Data Sets 131, 141, 151 - Technology Parameters 2: Reading/Writing Set 1, 2, 3 - Siemens SIRIUS 3RW44 System Manual

Soft starters
Hide thumbs Also See for SIRIUS 3RW44:
Table of Contents

Advertisement

PROFIBUS DP Communication Module

8.12.15 Data Sets 131, 141, 151 - Technology Parameters 2: Reading/Writing Set 1, 2, 3

ID
Bit
No
Byte
.
120 4 - 7
Device function_2
1
8 - 11
Device function_1
130 12
Rated operating current I
0
3
16
Load type
1
4
16
Protection against voltage failure
2-7
16
Reserved = 0
136 17
Prewarning motor temperature
0-2
5
18
Response to overload - thermal motor model
3-7
18
Reserved = 0
0-4
6
19
Tripping class
5-7
19
Reserved = 0
7
20
Pre-charge time
8
21
Idle time
137 22-23
Prewarning limit - tripping reserve
0-1
10
24
Response to overload - temperature sensor
2-3
24
Reserved = 0
4-6
9
24
Temperature sensor
8-62
Bit
Byte
Value
Preamble
0
Coordination
1 - 3
Reserved = 0
Meaning
e
Writing 0x20 via channel C1 (PLC)
Writing 0x30 via channel C2 (PC)
Writing 0x40 via device interface (PC)
Only
for
data
Value range [coding]
set
131
x
x
0 ... 2 000 A [0 ... 200 000]
x
3-phase [0]
x
• No [0]
• Yes [1]
x
0 ... 95 % [0 ... 19]
x
• Tripping without restart [0]
• Tripping with restart [1]
• Warning [2]
x
• CLASS 5 (10a) [3]
• CLASS 10 [0]
• CLASS 15 [4]
• CLASS 20 [1]
• CLASS 30 [2]
• CLASS OFF [15]
x
60 ... 1 800 s [2 ... 60]
x
0 ... 255 s [0 ... 255]
x
0 ... 500 s [0 ... 500]
x
• Tripping without
restart [0]
• Tripping with restart [1]
• Warning [2]
x
• Deactivated [0]
• Thermoclick [1]
• PTC - type A [2]
Comment
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
Factor
0.01 A
5 %
30 s
1 s
1 s

Advertisement

Table of Contents
loading

Table of Contents