5.5

Other Device Functions

5.5.1 Measurement-value Display

SIEMENS
3RW44
Menu
ESC
OK
OK
1
Display mea-
sured value
select
ESC
OK
OK
1
Phase
voltages
select
ESC
OK
2
Phase-to-pha-
se voltages
select
ESC
OK
3
Blocking
voltages
select
ESC
OK
4
Phase
currents
select
ESC
OK
5
Power
0 W
default
ESC
OK
6
Line frequency
0 Hz
default
ESC
OK
7
Supply voltage
230 V
default
ESC
OK
8
Heatsink
temperature
22 °C
default
ESC
OK
9
Motor heat
build-up
0 %
default
ESC
OK
10
Remaining time
for tripping
65540 s
default
ESC
OK
Function call
Switch off
standard display
OK
ESC
OK
OK
Switch off
standard display
execute ?
ESC
Figure 5-32:Measurement-value display
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
Note
When using the 3RW44 soft starter in an IT system with ground fault
monitoring: 3RW44, product version ≤ *E06* and the PROFIBUS DP
communication module may not be used in this network configuration.
3RW44 soft starters as of product version *E07* can be used in
combination with the PROFIBUS DP communication module. However,
the phase voltage values (UL-N) and phase-to-phase voltage values (UL-
L) may be displayed incorrectly on the measurement-value display of the
3RW44.
Note
The "Phase currents" display always shows the currents in the supply
cable. That is, if the soft starter is operated in the "Inside delta circuit"
circuit type, the currents measured internally by the soft starter are
extrapolated to the supply cable current (phase current) by a factor of 1.73
and displayed.
Due to asymmetries, the phase currents in the inside delta circuit may
deviate from the currents running through the supply cables.
accept
OK
OK
Commissioning
5-41