Installation, Connection and Branch Layout

3.2.3 Soft Starters in Inside Delta Circuits

Prerequisite
Example
3-6
A motor whose windings can be connected in a delta circuit where a supply
voltage prevails.
Supply voltage:
Rated motor current:
Current via soft starter in an inside delta circuit
Selected soft starter in an inside delta circuit
Figure 3-4:Name plate of a 22 kW motor
The SIRIUS 3RW44 soft starter can be dimensioned to match the current flowing
in the motor section (58 % of the conductor current) by connecting it in the delta
winding of the motor. This requires at least 6 motor lines.
The 3RW44 soft starter automatically detects how it is connected so the
connection type does not have to be explicitly set on the device. The detected
connection type can be read on the starter under the menu item "Status display/
Connection type". In this case the display reads "Inside delta circuit". If the
circuitry is faulty or the motor is not connected, the display shows "Unknown".
Notice
The rated motor current given on the name plate should always be set in the
quickstart menu or in the motor adjustment menu item. This setting is
independent of the type of connection of the soft starter.
Value to be set in the above example for a supply voltage of 400 V, e.g. 40.5 A.
400 V
40.5 A
approx.
24 A
3RW44 22
typenschild.jpg
SIRIUS 3RW44 System Manual