Siemens SIRIUS 3RW44 System Manual page 176

Soft starters
Hide thumbs Also See for SIRIUS 3RW44:
Table of Contents

Advertisement

PROFIBUS DP Communication Module
ID
Bit
Byte
No.:
4-7
8
Reserved = 0
Device function
0-2
9
Reserved = 0
3
369
9
Factory settings restored
4-7
9
Reserved = 0
367
10
Faulty parameter number (low byte) —
11
Faulty parameter number (high
byte)
0-1
12
Reserved = 0
2
1421 12
Impermissible Ie/CLASS settings
3-7
12
Reserved = 0
0
1449 13
Parameter set 1 active
1
1450 13
Parameter set 2 active
2
1451 13
Parameter set 3 active
3
13
Reserved = 0
4
1453 13
Impermissible change of the
parameter set
5-7
13
Reserved = 0
0-1
14
Reserved = 0
2
1404 14
Motor heating active
3
1402 14
DC braking active
4
1403 14
Dynamic DC braking active
5
1471 14
Motor connection method star/delta —
6
1472 14
Motor connection method inside
delta
7
1473 14
Motor connection method unknown
0
1408 15
No load
1
15
Reserved = 0
2
1409 15
Loss of phase L1
3
1410 15
Loss of phase L2
4
1411 15
Loss of phase L3
5
1412 15
Line phase direction right
6
1413 15
Line phase direction left
7
15
Reserved = 0
16
Reserved = 0
0
1435 17
Output 1 active
1
1436 17
Output 2 active
2
1437 17
Output 3 active
8-52
Signal bit
E
Meaning/Acknowledgment
*)
No.
The signal bit is always deleted after acknowledgement
with "Trip reset".
In connection with byte 8
of the first parameter not accepted.
The signal byte is always deleted after
acknowledgement with "Trip reset".
1
2
and 8
, states the ID number
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04