PROFIBUS DP Communication Module
8-20
**) Notice
During parameterization with the GSD file it is possible to select values that are
dependent on each other, but which are not permissible in combination. The
respective parameter is reported as "Incorrect parameter value" in data set 92.
The following table shows which parameters are dependent on each other and
how these have to be set:
Parameter
Rated operating current I
Maximum current limit
Maximum starting time
Limiting torque
Table 8-4: Interdependent parameter settings
Depends on
e
Greater than
Greater than
Greater than
Settings
Tripping class CLASS (refer to
Chapter 10.3.2 "Technical Data
Power Unit" on Page 10-8).
Minimum current limit Chapter 5.4.6
"Specifying Current Limits" on Page
5-27.
Starting time Chapter 5.4.3
"Specifying the Starting Mode" on
Page 5-13.
Start torque Chapter 5.4.3
"Specifying the Starting Mode" on
Page 5-13, torque control and torque
control with current limiting.
SIRIUS 3RW44 System Manual