Cross-Country Fault Example - GE L90 Instruction Manual

Line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

SINGLE-POLE TRIPPING

10.5.6 Cross-country fault example

Assume a single pole operation application where L90 relays are used to protect a two-terminal line, (terminals T1 and T2)
using phase and ground distance zone 1, 2, and 3 elements in a permissive over-reaching transfer trip scheme. The
performance of the system with one, two, and four-bit communications channels is outlined for a mid-line phase A-to-
ground fault and a co-incident phase B-to-ground fault just behind terminal T2. Assume also that the reclosers are enabled
and reset.
At T1 the following protection elements pick up:
Ground Distance Zone 1, 2, and 3 for an AG fault
Ground Distance Zone 2 and 3 for a BG fault
Phase Distance Zone 2 and 3 for an AB fault
At T1, the phase selector determines the fault is type ABG. This response is independent from the distance elements; the
Phase Selector sees two forward faults.
At T2, the following protection elements pick up:
Ground Distance Zone 1, 2, and 3 for an AG fault
At T2 the phase selector determines the fault is type AG. The reverse BG fault is likely to be ignored.
If a one-bit channel is used, terminal T1 trips three poles but terminal T2 trips phase A only, which is undesirable. See the
table.
Table 10-34: One-bit channel tripping
Terminal
Remote data
Bit pattern received
RX1
T1
1
T2
1
If a two-bit channel is used, both terminals trip phase A only, which is desired. See the following table.
Table 10-35: Two-bit channel tripping
Terminal
Remote data
Bit pattern received
RX1
T1
1
T2
1
If a four-bit channel is used, both terminals trip phase A only, which is desired. See the following table.
Table 10-36: Four-bit channel tripping
Terminal
Remote data
Bit pattern received
RX1
T1
0
T2
1
10
10-50
Remote
determination of
fault type
Any
Any
Remote
determination of
RX2
fault type
0
AG
1
ABG
RX2
RX3
RX4
0
0
1
0
0
0
Local data
Local determination
Trip output
of fault type
MULTI-P (ABG)
Trip Three Phases
AG
Trip Phase A
Local data
Local determination
Trip output
of fault type
ABG
Trip Phase A
AG
Trip Phase A
Local data
Remote
Local determination
determination Of
of fault type
fault type
AG
ABG
ABG
AG
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 10: THEORY OF OPERATION
Trip output
Trip Phase A
Trip Phase A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents