GROUPED ELEMENTS
The distance zones of the L90 are identical to that of the D60 Line Distance Relay.
The figure shows a condition for the L90 only that forces distance to be self-polarized to assure correct distance operation
when L90 relays are synchronizing to each other.
5.7.5.2 Phase distance (ANSI 21P, IEC PDIS)
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) DISTANCE PHASE DISTANCE Z1(Z5)
5
PHASE DISTANCE Z1
5-206
Figure 5-100: Memory voltage logic
PHS DIST Z1
FUNCTION: Disabled
PHS DIST Z1 DIR:
Forward
PHS DIST Z1
SHAPE: Mho
PHS DIST Z1 XFMR VOL
CONNECTION: None
PHS DIST Z1 XFMR CUR
CONNECTION: None
PHS DIST Z1
REACH: 2.00 Ω
PHS DIST Z1
RCA: 85°
PHS DIST Z1 REV
REACH: 2.00 Ω
PHS DIST Z1 REV
REACH RCA: 85°
PHS DIST Z1
COMP LIMIT: 90°
PHS DIST Z1
DIR RCA: 85°
PHS DIST Z1
DIR COMP LIMIT: 90°
PHS DIST Z1 QUAD
RGT BLD: 10.00 Ω
Range: Disabled, Enabled
Range: Forward, Reverse, Non-directional
Range: Mho, Quad
Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1,
Yd3, Yd5, Yd7, Yd9, Yd11
Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1,
Yd3, Yd5, Yd7, Yd9, Yd11
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 30 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS