CHAPTER 5: SETTINGS
5.7.3 Line differential elements
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) LINE DIFFERENTIAL ELEMENTS
LINE DIFFERENTIAL
ELEMENTS
5.7.3.1 Current differential (ANSI 87L)
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) LINE DIFFERENTIAL... CURRENT DIFFERENTIAL
CURRENT
DIFFERENTIAL
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CURRENT
DIFFERENTIAL
STUB BUS
CURRENT DIFF
FUNCTION: Disabled
CURRENT DIFF SIGNAL
SOURCE 1: SRC 1
CURRENT DIFF SIGNAL
SOURCE 2: None
CURRENT DIFF SIGNAL
SOURCE 3: None
CURRENT DIFF SIGNAL
SOURCE 4: None
CURRENT DIFF BLOCK:
Off
CURRENT DIFF
PICKUP: 0.20 pu
CURRENT DIFF
CT TAP 1: 1.00
CURRENT DIFF
CT TAP 2: 1.00
CURRENT DIFF
RESTRAINT 1: 30%
CURRENT DIFF
RESTRAINT 2: 50%
CURRENT DIFF
BREAK PT: 1.0 pu
INRUSH INHIBIT MODE:
Disabled
INRUSH INHIBIT
LEVEL: 20% fo
CURRENT DIFF GND
FUNCTION: Disabled
CURRENT DIFF GND
PICKUP: 0.10 pu
CURRENT DIFF GND
RESTRAINT: 25%
CURRENT DIFF GND
DELAY: 0.10 s
CURRENT DIFF DTT:
Enabled
GROUPED ELEMENTS
See below
See page 5-201
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: None, SRC 1, SRC 2, SRC 3, SRC 4
Range: None, SRC 1, SRC 2, SRC 3, SRC 4
Range: None, SRC 1, SRC 2, SRC 3, SRC 4
Range: FlexLogic operand
Range: 0.10 to 4.00 pu in steps of 0.01
Range: 0.20 to 5.00 in steps of 0.01
Range: 0.20 to 5.00 in steps of 0.01
Range: 1 to 50% in steps of 1
Range: 1 to 70% in steps of 1
Range: 0.0 to 20.0 pu in steps of 0.1
Range: Disabled, Per phase, 2-out-of-3, Average
Range: 1.0 to 40.0% f
in steps of 0.1
0
Range: Disabled, Enabled
Range: 0.05 to 1.00 pu in steps of 0.01
Range: 1 to 50% in steps of 1
Range: 0.00 to 5.00 s in steps of 0.01
Range: Disabled, Enabled
5
5-197