GE L90 Instruction Manual page 253

Line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
in the integer result. The FlexElement Base Units table in the Settings > FlexLogic > FlexElements section later, which
tabulates the per-unit base value used by its pickup setting and implies the per-unit base used by other FlexAnalogs, can
be of use in selecting a value for the RxGOOSE Analog1 PU setting.
Some UR elements have requirements for the type of input operands, for instance current type or voltage type. These
elements assume that RxGOOSE Analog operands are of whatever type is necessary to meet these requirements.
The per-unit base setting represents thousands, not single units. For example, a PU base of 1.000 is actually 1000 and a
PU base of 0.001 is 1.
When using RxGOOSE Analogs and PU base in FlexElements, the largest value that can be displayed in the FlexElement
actual values is 2,140,000.000.
Reports
Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports.
Report settings
Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports > Report Settings.
ReportSettings rptID
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the RptID attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false. The RptID is the name of the report.
ReportSettings optFields
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the OptFlds attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings bufTime
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the BufTm attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings trgOps
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the TrgOps attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings intgPd
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the IntgPd attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
Buffered and unbuffered reports
Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports > Buffered Reports or Unbuffered
Reports.
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
5
5-67