GE L90 Instruction Manual page 219

Line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
 NETWORK PORT 3
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, HTTP, and PRP protocols. PRP is
explained in its own section later.
Use the front panel to change these settings. When online, the EnerVista software can be used to enable/disable each port
only. In the Offline Window area, all settings can be changed except port 2 redundancy.
— This setting sets the port's IPv4 address in standard IPV4 format. This setting is valid on port 3 if
PRT1 (2 or 3) IP ADDRESS
port 2
is set to None.
REDUNDANCY
— This setting sets the port's IPv4 subnet mask in standard IPV4 format. This setting is valid on
PRT1 (2 or 3) SUBNET MASK
port 3 if port 2
is set to None.
REDUNDANCY
— This setting enable/disables network communication on the respective port. When the port
PRT1 (2 or 3) FUNCTION
function is Disabled, the network traffic on this port is disabled. The PRT2 redundancy setting has no effect on this
functionality. The change takes effect upon relay restart.
— Determines if ports 2 and 3 operate in redundant or independent mode. If a license for PRP was
PRT2 REDUNDANCY
purchased, the options are None, Failover, and PRP. If a license for PRP was not purchased, the options are None and
Failover. In non-redundant mode (
and mask addresses. If
REDUNDANCY
Ports 2 and 3 use the port 2 MAC address, IP address, and mask
The configuration fields for IP address and mask on port 3 are hidden
Port 3 is in standby mode and does not actively communicate on the Ethernet network but monitors its link to the
Multilink switch. If port 2 detects a problem with the link, communications is switched to Port 3. Port 3 is, in effect,
acting as a redundant or backup link to the network for port 2. Once port 2 detects that the link between itself and the
switch is good and that communication is healthy for five minutes, then switching back to port 2 is performed. The
delay in switching back ensures that rebooted switching devices connected to the L90, which signal their ports as
active prior to being completely functional, have time to completely initialize themselves and become active. Once
port 2 is active again, port 3 returns to standby mode.
If
is set to PRP, the operation of ports 2 and 3 is as follows:
REDUNDANCY
Ports 2 and 3 use the port 2 MAC address, IP address, and mask
The configuration fields for IP address and mask on port 3 are overwritten with those from port 2. This is visible on the
front panel but not displayed in the EnerVista software.
Port 2
field is visible
MCST ADDRESS
The port 2 PTP function still uses only port 2 and the port 3 PTP function still uses only port 3. The relay still
synchronizes to whichever port has the best master. When ports 2 and 3 see the same master, as is typically the case
for PRP networks, the port with the better connectivity is used.
Behavior for GOOSE messages is as follows:
If
is set to Failover or PRP, In order to transmit a GOOSE message on port 2, the CID file must be
REDUNDANCY
configured to have the corresponding GSE element in both ConnectedAPs S2 and S3. In the EnerVista software, the
TxGOOSE PORT ASSIGNMENT
GOOSE only on port 2, with failover/ PRP.
If
is set to PRP, the port 2 configured GOOSE message is simultaneously transmitted on ports 2 and 3
REDUNDANCY
If
is set to failover and the port 2 link fails, then only the port 2 configured GOOSE message is transmitted
REDUNDANCY
on port 3
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRT3 IP ADDRESS:
127.0.0.1
PRT3 SUBNET IP MASK:
255.0.0.0
PRT3 FUNCTION:
Enabled
set to None), ports 2 and 3 operate independently with their own MAC, IP,
REDUNDANCY
is set to Failover, the operation of ports 2 and 3 is as follows:
needs to be "Ports-1,2,3" to transmit GOOSE on both ports 1 and 2, or "Ports-2,3" to have
Range: standard IPV4 address format
Range: standard IPV4 address format
Range: Enabled, Disabled
PRODUCT SETUP
5
5-33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents