CONTROL ELEMENTS
5
5.8.11.8 Open pole detector
SETTINGS CONTROL ELEMENTS MONITORING ELEMENTS OPEN POLE
OPEN POLE
5-346
Figure 5-198: VT fuse fail logic
OPEN POLE FUNCTION:
Disabled
OPEN POLE BLOCK:
Off
OPEN POLE VOLTAGE
SUPV: Disabled
OPEN POLE CURRENT
PKP: 0.050 pu
OPEN POLE LINE XC1:
9999.9 Ω
OPEN POLE LINE XC0:
9999.9 Ω
OPEN POLE REM CURR
PKP: 0.050 pu
OPEN POLE MODE:
Accelerated
Range: Disabled, Enabled
Range: FlexLogic operand
Range: Disabled, Enabled
Range: 0.020 to 30.000 pu in steps of 0.001
Range: 300.0 to 9999.9 ohms in steps of 0.001
Range: 300.0 to 9999.9 ohms in steps of 0.001
Range: 0.020 to 30.000 pu in steps of 0.001
Range: Accelerated, Traditional
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL