INPUTS/OUTPUTS
FREQ RATE 1 MAX FREQUENCY
The setting can be used to effectively block the feature based on frequency. For example, if the intent is to monitor a
decreasing trend but only if the frequency is already below a certain level (such as for load shedding), set this setting to the
required frequency level.
If the signal source assigned to the frequency rate of change element is only set to auxiliary VT, then the minimum
voltage supervision is 3 V.
5
5.9 Inputs/outputs
5.9.1 Contact inputs
SETTINGS INPUTS/OUTPUTS CONTACT INPUTS
CONTACT INPUTS
5-392
— This setting defines the maximum frequency level required for operation of the element.
Figure 5-217: Frequency rate of change logic
CONTACT INPUT H5a
↓
CONTACT INPUT xxx
CONTACT INPUT
THRESHOLDS
CONTACT INPUT H5a ID:
Range: up to 20 alphanumeric
Cont Ip 1
characters
CONTACT INPUT H5a
Range: 0.0 to 16.0 ms in steps of 0.5
DEBNCE TIME: 6.0 ms
CONTACT INPUT H5a
Range: Disabled, Enabled
EVENTS: Disabled
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS