GE L90 Instruction Manual page 484

Line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

GROUPED ELEMENTS
5.7.15.3 87L trip
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  SUPERVISING ELEMENTS  87L TRIP
 87L TRIP
5
The 87L trip element must be used to secure the generation of tripping outputs. It is especially recommended for use in all
single-pole tripping applications. It provides the capability of maintaining the trip signal while the fault current is still
flowing, to choose single-pole or three-pole tripping, to employ the received direct transfer trip (DTT) signals, and to assign
supervising trip elements like the disturbance detector. The logic is used to ensure that the relay
Trips the faulted phase for a single line to ground fault, as detected by the line differential element
Trips all three phases for any internal multiphase fault
Trips all three phases for a second single line to ground fault during or following a single pole trip cycle
For maximum security, it is recommended that the disturbance detector (plus other elements if required) be assigned to
see a change in system status before a trip output is permitted. This ensures the relay does not issue a trip signal as a
result of incorrect settings, incorrect manipulations with a relay, or inter-relay communications problems (for example,
extremely noisy channels). The open pole detector provides forcing of three-pole tripping for sequential faults and close-
onto-fault if wanted. The open pole detector feature must be employed and adequately programmed for proper operation
of this feature. The
autoreclosing.
If a direct transfer trip (DTT) is not required for the 87L trip scheme to operate, disable it at the remote relay via the
GROUPED ELEMENTS  SETTING GROUP 1(6)  LINE DIFFERENTIAL ELEMENT  CURRENT DIFFERENTIAL
menu.
87L TRIP FUNCTION
— Assigns a source for the seal-in function.
87L TRIP SOURCE
— Selects either three-pole or single-pole mode of operation.
87L TRIP MODE
— Assigns a trip supervising element. The
87L TRIP SUPV
enabled); otherwise, elements like instantaneous overcurrent, distance, and so can be used.
5-298
87L TRIP FUNCTION:
Disabled
87L TRIP SOURCE:
SRC 1
87LP TRIP MODE:
3-Pole
87LG TRIP MODE:
3-Pole
87LP TRIP SUPV:
Off
87LG TRIP SUPV:
Off
87L TRIP FORCE 3Φ:
Off
87L TRIP SEAL-IN:
Disabled
87L TRIP SEAL-IN
PICKUP: 0.20 pu
87L TRIP TARGET:
Self-reset
87L TRIP EVENTS:
Disabled
and
87L TRIP 1P OP
87L TRIP 3P OP
— This setting is used to enable or disable the element.
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 3-Pole, 1-Pole
Range: 3-Pole, 1-Pole
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Disabled, Enabled
Range: 0.20 to 0.80 pu in steps of 0.01
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
operands are provided to initiate single-pole or three-pole
FlexLogic operand is recommended (the element has to be
50DD SV
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS