CHAPTER 5: SETTINGS
5.8.12.3 Permissive under-reaching transfer trip (PUTT)
SETTINGS  CONTROL ELEMENTS  PILOT SCHEMES  PUTT SCHEME
 PUTT SCHEME
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
Figure 5-204: DUTT scheme logic
PUTT SCHEME
FUNCTION: Disabled
PUTT SCHEME BLOCK:
Off
PUTT RX PICKUP
DELAY: 0.000 s
PUTT SEAL-IN
DELAY: 0.010 s
PUTT NO OF COMM
BITS: 1
PUTT RX1:
Off
PUTT RX2:
Off
Range: Disabled, Enabled
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 1, 2, or 4
Range: FlexLogic operand
Range: FlexLogic operand
CONTROL ELEMENTS
5
5-357