Emerson Rosemount 3051S Reference Manual page 67

Electronic remote sensors
Hide thumbs Also See for Rosemount 3051S:
Table of Contents

Advertisement

Reference Manual
00809-0100-4804, Rev AA
January 2011
Dynamic Performance
(1) Consult Instrument Toolkit for 3051S ERS configurations that include remote seals.
Ambient Temperature Effects per 50 °F (28 °C)
Coplanar Gage Sensor (3051SAM_ _G)
Ultra
±(0.009% URL + 0.025% Span) from 1:1 to 10:1
Range 2-5
±(0.018% URL + 0.05% Span) from >10:1 to 200:1
Coplanar Absolute Sensor (3051SAM_ _A)
Ultra
±(0.0125% URL + 0.0625% Span) from 1:1 to 5:1
Ranges 1-4
±(0.025% URL + 0.125% Span) from >5:1 to 100:1
In-Line Gage Sensor (3051SAM_ _T)
In-Line Absolute Sensor (3051SAM _ _E)
Ultra
Ranges 2-4
±(0.009% URL + 0.025% Span) from 1:1 to 10:1
±(0.018% URL + 0.08% Span) from >10:1 to 100:1
Ranges 5
±(0.05% URL + 0.075% Span) from 1:1 to 10:1
±(0.0125% URL + 0.0625% Span) from 1:1 to 5:1
Ranges 1
±(0.025% URL + 0.125% Span) from >5:1 to 100:1
Liquid Level Sensor (3051SAL)
Ultra
Ranges 1-5
Consult Instrument Toolkit
(1) Ambient Temperature Effects specifications are for each gage / absolute pressure sensor of the ERS System and are not reflective of the DP
calculation.
Mounting Position Effects
Coplanar Gage Sensor (3051SAM_ _G)
Zero shifts up to ±1.25 inH
Span: no effect
Coplanar Absolute Sensor (3051SAM_ _A)
Zero shifts up to ±2.5 inH
Span: no effect
In-Line Gage Sensor (3051SAM_ _T)
In-Line Absolute Sensor (3051SAM _ _E)
Zero shifts up to ±2.5 inH
Span: no effect
Liquid Level Sensor (3051SAL)
With remote seal diaphragm in vertical plane, zero shifts of up to ±1 inH
With remote seal diaphragm in horizontal plane, zero shifts of up to ±5 inH
Span: no effect
(1) Mounting Position Effects specifications are for each gage / absolute pressure sensor of the ERS System and are not reflective of the DP calculation.
(1)
Total Time Response at 75 °F (24 °C), Includes Dead Time: 360 ms
Dead Time (nominal): 220 ms
Update Rate: 11 updates per second
(1)
O (3,11 mbar), which can be zeroed
2
O (6,22 mbar), which can be zeroed
2
O (6,22 mbar), which can be zeroed
2
Rosemount 3051S ERS System
(1)
Classic
±(0.0125% URL + 0.0625% Span) from 1:1 to 5:1
±(0.025% URL + 0.125% Span) from >5:1 to 100:1
Classic
±(0.0125% URL + 0.0625% Span) from 1:1 to 5:1
±(0.025% URL + 0.125% Span) from >5:1 to 100:1
Classic
±(0.0125% URL + 0.0625% Span) from 1:1 to 5:1
±(0.025% URL + 0.125% Span) from >5:1 to 100:1
±(0.05% URL + 0.075% Span) from 1:1 to 10:1
±(0.0125% URL + 0.0625% Span) from 1:1 to 5:1
±(0.025% URL + 0.125% Span) from >5:1 to 100:1
Classic
Consult Instrument Toolkit
O (2,5 mbar), which can be zeroed
2
O (12,5 mbar), which can be zeroed
2
A-3