Using an AGS Module: Setup
7.1

Setting Up the AGS using the ME-ARC

Press the SETUP button on the ME-ARC remote, and then rotate the SELECT knob to the 04 AGS
Setup display. The menus available from this screen allow the generator to be automatically
started and stopped based on many different conditions. From Table 7-2, determine the specifi c
autostart and autostop conditions with which you want the generator to be automatically con-
trolled, and then use that specifi c menu setting to confi gure the AGS.
Info: For information on using the CTRL, METER, and TECH button menus, refer to
Section 7.2 "Operating/Monitoring the AGS using the ME-ARC".
Info: The Auto Connect setting must be selected from the CTRL: 01 ACIn Control menu
if a ME-AGS-N is installed and enabled in the system. Otherwise, when the generator
is autostarted it may be prevented from connecting because the criteria to allow the
AC input to connect (02C AC In - Time, 02D AC In - VDC, or 02E AC In - SOC) may not
have been met.
Note: This is true unless you are using an inverter that has two independent AC
inputs—one for grid and the other for generator (i.e., MSH4024RE). On the MSH4024RE
inverter, the AC In control features only work with the GRID IN (AC1) input.

Table 7-2, ME-ARC Autostart/Autostop Matrix

Autostart Condition
Starts on low battery volt-
age (DC voltage connected
to Terminals #3 and #4)
Starts daily at a set time
Starts on high AC amps to
an inverter load¹
Starts when the battery
SOC² is low
Starts when temperature
increases
Starts when battery SOC²
has been <100% for a set
# of days
Note¹: Only applicable to MS-PAE, MS-PE and MSH inverters.
Note²: Autostart/stop conditions using SOC require a ME-BMK to be installed.
Page 59
Autostop Condition
Stops on higher battery voltage
Stops at Float charge after a set
time period (using Absorb Done
Time setting)
Stops at Float charge after bat-
tery current requirement is low
(using Absorb Done Amps)
Stops at Float charge using a bat-
tery SOC setting (using Absorb
Done SOC setting)²
Stops daily at a different set time
Stops on lower AC amps to an
inverter load¹
Stops when the battery SOC² is
higher
Stops after a set time period
Stops when battery SOC² is
100%
SETUP Menu
04A Gen Run VDC
04A Gen Run VDC
(Set to Float)
04A Gen Run VDC
(Set to Float)
04A Gen Run VDC
(Set to Float)
04B Gen Run Time
04C Gen Run Amps
04D Gen Run SOC
04E Gen Run Temp
04K Gen 100%
SOC Start Days
© 2014 Magnum Energy, Inc.
Page
60
60
60
60
62
62
63
64
70