Magnum Energy ME-ARC50 Owner's Manual page 135

Me-arc series. advanced remote control. version 4.0 or higher: with ags, bmk, acld, and pt info
Hide thumbs Also See for ME-ARC50:
Table of Contents

Advertisement

Menu
Main
Menu
Heading/Item
03C Battery Type
03
Char-
ger
Setup
03D Absorb Done
03E Max Charge Rate
03F Max Charge Time OFF, 0.1-25.5 Hrs
03G Final Charge
Stage
03H EQ Reminder
Days
04A Gen Run VDC
04
04B Gen Run Time
AGS
Setup
04C Gen Run Amps
© 2014 Magnum Energy, Inc.
Appendix A – ME-ARC Compatibility Matrix
Features/Settings
Selections/
Adjustments Range
Gel, Flooded, AGM1, AGM2
Absorb (12.0-16.0)*
Float (12.0-16.0)*
EQ (12.0-16.0)*
EQ Done (0.1-25.5)
Max Charge =
OFF, 20-990ADC
CV Charge =
12.0-16.0* VDC
CV Chg Done = Time,
Amps, Hold CV Chg VDC
Time = 0.1-25.5
Max CC/CV Time =
CC/
OFF, 0.1-25.5 Hrs
CV
Recharge Volts =
12.0-16.0* VDC
Amps = 0-250 ADC
Max CC/CV Time =
OFF, 0.1-25.5 Hrs
Recharge Volts =
12.0-16.0* VDC
Hold CV Chg VDC
Time = 0.1-25.5 Hrs
Amps = 0-250 ADC
SOC = 50-100%
10-100%
0-100%
Multi, Float
Silent Rebulk = 12-16V*
OFF, 1-255 Days
Start Volts = OFF, 9.0-15.9*
Start Delay = 0-127s, 1-127m
Stop = 9.1-16.0*, Float
Stop Delay = 0-127s, 1-127m
OFF, ON – Start Time =
12:00A-11:45P
Stop Time = 12:00A-11:45P
Start Amps = OFF, 5-60A
Start Delay = 0-127s, 1-127m
Stop Amps = 4-59A
Stop Delay = 0-127s, 1-127m
Model/
Level
Default
Required
≥Level 1
Flooded
14.4*
13.2*
≥Level 3 [2]
15.6*
4.0 Hrs
200ADC
13.8*V
Time
2 Hrs
12 Hrs
≥Level 4
12.0*V
20 ADC
12 Hrs
12.0*V
≥Level 4 [4]
2.0 Hrs
≥Level 4 [5]
20 ADC
≥Level 4 [5]
100%
≥Level 2
100%
≥Level 3
≥Level 4 [5]
12.0 Hrs
≥Level 4 [5]
Multi
≥Level 4
12.0*V
≥Level 1
OFF
11.5*V
120 Sec
≥Level 1
14.4*V
120 Sec
OFF
≥Level 1
12:00A
OFF
120 Sec
≥Level 4
4A
120 Sec
Page 128

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents