B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 56 of 62)
ADDR
REGISTER NAME
CA6E
...Repeated for Direct Output 48
CA70
...Repeated for Direct Output 49
CA72
...Repeated for Direct Output 50
CA74
...Repeated for Direct Output 51
CA76
...Repeated for Direct Output 52
B
CA78
...Repeated for Direct Output 53
CA7A
...Repeated for Direct Output 54
CA7C
...Repeated for Direct Output 55
CA7E
...Repeated for Direct Output 56
CA80
...Repeated for Direct Output 57
CA82
...Repeated for Direct Output 58
CA84
...Repeated for Direct Output 59
CA86
...Repeated for Direct Output 60
CA88
...Repeated for Direct Output 61
CA8A
...Repeated for Direct Output 62
CA8C
...Repeated for Direct Output 63
CA8E
...Repeated for Direct Output 64
Direct Input/Output Alarms (Read/Write Setting)
CAD0
Direct Input/Output Channel 1 CRC Alarm Function
CAD1
Direct Input/Output Channel 1 CRC Alarm Message
Count
CAD2
Direct Input/Output Channel 1 CRC Alarm Threshold
CAD3
Direct Input/Output Channel 1 CRC Alarm Events
CAD4
Reserved (4 items)
CAD8
Direct Input/Output Channel 2 CRC Alarm Function
CAD9
Direct Input/Output Channel 2 CRC Alarm Message
Count
CADA
Direct Input/Output Channel 2 CRC Alarm Threshold
CADB
Direct Input/Output Channel 2 CRC Alarm Events
CADC
Reserved (4 items)
CAE0
Direct Input/Output Channel 1 Unreturned Messages
Alarm Function
CAE1
Direct Input/Output Channel 1 Unreturned Messages
Alarm Msg Count
CAE2
Direct Input/Output Channel 1 Unreturned Messages
Alarm Threshold
CAE3
Direct Input/Output Channel 1 Unreturned Messages
Alarm Events
CAE4
Reserved (4 items)
CAE8
Direct Input/Output Channel 2 Unreturned Messages
Alarm Function
CAE9
Direct Input/Output Channel 2 Unreturned Messages
Alarm Msg Count
CAEA
Direct Input/Output Channel 2 Unreturned Messages
Alarm Threshold
CAEB
Direct Input/Output Channel 2 Unreturned Messages
Alarm Events
CAEC
Reserved (4 items)
Remote Devices (Read/Write Setting) (16 modules)
CB00
Remote Device 1 GSSE/GOOSE Application ID (GOID)
CB21
Remote Device 1 GOOSE Ethernet APPID
CB22
Remote Device 1 GOOSE Dataset
CB23
Remote Device 1 in PMU Scheme
CB24
...Repeated for Device 2
CB48
...Repeated for Device 3
CB6C
...Repeated for Device 4
CB90
...Repeated for Device 5
CBB4
...Repeated for Device 6
B-64
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
0 to 1
---
100 to 10000
---
1 to 1000
---
0 to 1
---
1 to 1000
---
0 to 1
---
100 to 10000
---
1 to 1000
---
0 to 1
---
1 to 1000
---
0 to 1
---
100 to 10000
---
1 to 1000
---
0 to 1
---
1 to 1000
---
0 to 1
---
100 to 10000
---
1 to 1000
---
0 to 1
---
1 to 1000
---
---
---
---
0 to 16383
---
0 to 16
---
0 to 1
---
APPENDIX B
FORMAT
DEFAULT
1
F102
0 (Disabled)
1
F001
600
1
F001
10
1
F102
0 (Disabled)
1
F001
10
1
F102
0 (Disabled)
1
F001
600
1
F001
10
1
F102
0 (Disabled)
1
F001
10
1
F102
0 (Disabled)
1
F001
600
1
F001
10
1
F102
0 (Disabled)
1
F001
10
1
F102
0 (Disabled)
1
F001
600
1
F001
10
1
F102
0 (Disabled)
1
F001
10
F209
"Remote Device 1"
1
F001
0
1
F184
0 (Fixed)
1
F126
0 (No)