GE N60 Instruction Manual page 324

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5.8 INPUTS AND OUTPUTS
The direct analog outputs share the direct input and output settings for device ID, data rate, ring configuration, and channel
crossover.
ANALOG 1 VALUE: This setting selects the FlexAnalog parameter used to drive the associated direct analog output.
ANALOG 1 DEADBAND: This setting specifies the deadband value used to trigger transmission of the associated
direct analog output. This value is stored as an IEEE 754 / IEC 60559 floating-point number. Because of the large
range for this setting, not all values can be stored – some values may be rounded to the closest possible floating point
number.
ANALOG 1 TRIGGER: This setting selects the FlexLogic™ operand used to trigger the transmission of the associated
direct analog output. Transmission occurs on the rising edge of the operand. The operand must transition from 0 to 1
and remain at a value of 1 for at least one power system cycle to ensure detection of the rising edge and transmission
of the associated direct analog output.
c) DIRECT ANALOG INPUTS

PATH: SETTINGS
INPUTS/OUTPUTS
 DIRECT ANALOG 1
 INPUT
5
The direct analogs feature allows the transmission of analog values between any two UR-series relays supporting the fea-
ture. The communication channel is the same as that used for the direct inputs and outputs feature. When the direct inputs/
outputs and direct analog features are used together on the same channel, the UR-series relays must all be using firmware
version 5.20 or higher.
The settings for direct analog input 1 are described below. The description applies to all 32 direct analog inputs.
DIRECT ANALOG 1 DEVICE ID: This value selects the source of the direct analog 1 input. Direct analog input 1 is
driven by the device programmed in this setting.
DIRECT ANALOG 1 NUMBER: This value specifies which input to extract the value for the direct analog 1 input.
Direct analog input 1 is driven by the input programmed in this setting. This setting value corresponds to the direct ana-
log output number of the sending device.
DIRECT ANALOG 1 DEFAULT: This setting specifies the value of direct analog input 1 when the associated direct
device is offline and the
offline and the default mode is set to "Last Known", the value of direct analog input 1 remains at the last received value.
This value is stored as an IEEE 754 / IEC 60559 floating-point number. Because of the large range for this setting, not
all values can be stored – some values may be rounded to the closest possible floating point number.
DIRECT ANALOG 1 UNITS: This setting provides a four-character string that is used in the direct analog input 1 actual
values display.
DIRECT ANALOG 1 PU: This setting defines the per-unit base factor when using the
FlexAnalog™ value in other N60 features, such as FlexElements™. This value is used to normalize the direct analog
input 1 FlexAnalog™ quantity to its per-unit base. Refer to the FlexElements™ section for additional details on per-unit
base values.
5-194

DIRECT ANALOGS
DIRECT ANALOG 1
DEVICE: 0
DIRECT ANALOG 1
MESSAGE
NUMBER: 0
ANALOG 1 DEFAULT:
MESSAGE
1000.000
ANALOG 1 DEFAULT
MESSAGE
MODE: Default Value
DIRECT ANALOG 1
MESSAGE
UNITS: unit
DIRECT ANALOG 1 PU:
MESSAGE
1
DIRECT ANALOG 1 DEFAULT MODE
N60 Network Stability and Synchrophasor Measurement System
DIRECT ANALOG INPUTS
DIRECT ANALOG 1(32) INPUT
Range: 0 to 16 in steps of 1
Range: 0 to 32 in steps of 1
Range: –1000000000.000 to 1000000000.000 in steps
of 0.001
Range: Default Value, Last Known
Range: four alphanumeric characters
Range: 0 to 2000000 in steps of 1
is set to "Default Value". When the associated direct device is
5 SETTINGS
DIRECT ANALOG INPUT 1 ACTUAL
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents