GE N60 Instruction Manual page 460

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 30 of 62)
ADDR
REGISTER NAME
790C
...Repeated for PMU 4
Phasor Measurement Unit Recorder Configuration Counter Command (Read/Write Command) (4 modules)
7928
PMU 1 Recorder Clear Configuration Counter
7929
...Repeated for PMU 2
792A
...Repeated for PMU 3
B
792B
...Repeated for PMU 4
Phasor Measurement Unit Recording Values (Read Only) (4 modules)
792C
PMU 1 Available Records
792D
PMU 1 Second Per Record
792F
PMU 1 Last Cleared Date
7930
...Repeated for PMU 2
7934
...Repeated for PMU 3
7938
...Repeated for PMU 4
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
7940
PMU Network Reporting Function
7941
PMU Network Reporting ID Code
7942
PMU Network Reporting Rate
7943
PMU Network Reporting Style
7944
PMU Network Reporting Format
7945
PMU Network PDC Control
7946
PMU TCP Port Number
7947
PMU UDP Port Number 1
7948
PMU UDP Port Number 2
Phasor Measurement Unit Basic Configuration (Read/Write Setting) (4 modules)
7949
PMU 1 Function
794A
PMU 1 IDcode
794B
PMU 1 STN
7953
PMU 1 Source
7954
PMU 1 Post-Filter
7955
...Repeated for PMU 2
7961
...Repeated for PMU 3
796D
...Repeated for PMU 4
Phasor Measurement Unit Calibration (Read/Write Setting) (4 modules)
7979
PMU 1 Va Calibration Angle
797A
PMU 1 Vb Calibration Angle
797B
PMU 1 Vc Calibration Angle
797C
PMU 1 Vx Calibration Angle
797D
PMU 1 Ia Calibration Angle
797E
PMU 1 Ib Calibration Angle
797F
PMU 1 Ic Calibration Angle
7980
PMU 1 Ig Calibration Angle
7981
PMU 1 Sequence Voltage Shift Angle
7982
PMU 1 Sequence Current Shift Angle
7983
...Repeated for PMU 2
798D
...Repeated for PMU 3
7997
...Repeated for PMU 4
Phasor Measurement Unit Triggering (Read/Write Setting) (4 modules)
79A1
PMU 1 User Trigger
79A2
...Repeated for PMU 2
79A3
...Repeated for PMU 3
79A4
...Repeated for PMU 4
Phasor Measurement Unit Current Trigger (Read/Write Setting) (4 modules)
79A5
PMU 1 Current Trigger Function
79A6
PMU 1 Current Trigger Pickup
B-38
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
0 to 1
---
0 to 65535
---
0 to 6553.5
---
0 to 400000000
---
0 to 1
---
1 to 65534
---
0 to 11
---
0 to 1
---
0 to 1
---
0 to 1
---
1 to 65535
---
1 to 65535
---
1 to 65535
---
0 to 1
---
1 to 65534
---
---
---
0 to 5
---
0 to 5
---
-5 to 5
°
0.05
-5 to 5
°
0.05
-5 to 5
°
0.05
-5 to 5
°
0.05
-5 to 5
°
0.05
-5 to 5
°
0.05
-5 to 5
°
0.05
-5 to 5
°
0.05
-180 to 180
°
-180 to 180
°
0 to 65535
---
0 to 1
---
0.1 to 30
pu
0.001
APPENDIX B
FORMAT
DEFAULT
1
F126
0 (No)
1
F001
0
0.1
F003
0
1
F050
0
1
F102
0 (Disabled)
1
F001
1
1
F544
3 (5/sec.)
1
F546
0 (Polar)
1
F547
0 (Integer)
1
F102
0 (Disabled)
1
F001
4712
1
F001
4713
1
F001
4714
1
F102
0 (Disabled)
1
F001
1
---
F203
"GE-UR-PMU"
1
F167
0 (SRC 1)
1
F540
1 (Symm-3-point)
F002
0
F002
0
F002
0
F002
0
F002
0
F002
0
F002
0
F002
0
30
F002
0
30
F002
0
1
F300
0
1
F102
0 (Disabled)
F001
1800
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents