GE N60 Instruction Manual page 474

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 44 of 62)
ADDR
REGISTER NAME
AF56
...Repeated for IEC 61850 GGIO4 Analog Input 11
AF5D
...Repeated for IEC 61850 GGIO4 Analog Input 12
AF64
...Repeated for IEC 61850 GGIO4 Analog Input 13
AF6B
...Repeated for IEC 61850 GGIO4 Analog Input 14
AF72
...Repeated for IEC 61850 GGIO4 Analog Input 15
B
AF79
...Repeated for IEC 61850 GGIO4 Analog Input 16
AF80
...Repeated for IEC 61850 GGIO4 Analog Input 17
AF87
...Repeated for IEC 61850 GGIO4 Analog Input 18
AF8E
...Repeated for IEC 61850 GGIO4 Analog Input 19
AF95
...Repeated for IEC 61850 GGIO4 Analog Input 20
AF9C
...Repeated for IEC 61850 GGIO4 Analog Input 21
AFA3
...Repeated for IEC 61850 GGIO4 Analog Input 22
AFAA
...Repeated for IEC 61850 GGIO4 Analog Input 23
AFB1
...Repeated for IEC 61850 GGIO4 Analog Input 24
AFB8
...Repeated for IEC 61850 GGIO4 Analog Input 25
AFBF
...Repeated for IEC 61850 GGIO4 Analog Input 26
AFC6
...Repeated for IEC 61850 GGIO4 Analog Input 27
AFCD
...Repeated for IEC 61850 GGIO4 Analog Input 28
AFD4
...Repeated for IEC 61850 GGIO4 Analog Input 29
AFDB
...Repeated for IEC 61850 GGIO4 Analog Input 30
AFE2
...Repeated for IEC 61850 GGIO4 Analog Input 31
AFE9
...Repeated for IEC 61850 GGIO4 Analog Input 32
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
B01C
Default GOOSE/GSSE Update Time
B01D
IEC 61850 GSSE Function (GsEna)
B01E
IEC 61850 GSSE ID
B03F
IEC 61850 GOOSE Function (GoEna)
B040
IEC 61850 GSSE Destination MAC Address
B043
IEC 61850 Standard GOOSE ID
B064
IEC 61850 Standard GOOSE Destination MAC Address
B067
IEC 61850 GOOSE VLAN Transmit Priority
B068
IEC 61850 GOOSE VLAN ID
B069
IEC 61850 GOOSE ETYPE APPID
B06A
Reserved (2 items)
IEC 61850 Server Configuration (Read/Write Settings/Commands)
B06C
TCP Port Number for the IEC 61850 / MMS Protocol
B06D
IEC 61850 Logical Device Name
B07D
IEC 61850 Logical Device Instance
B08D
IEC 61850 LPHD Location
B0B5
Include Non-IEC 61850 Data
B06B
IEC 61850 Server Data Scanning Function
B0B7
Reserved (9 items)
IEC 61850 MMXU Deadbands (Read/Write Setting) (6 modules)
B0C0
IEC 61850 MMXU TotW Deadband 1
B0C2
IEC 61850 MMXU TotVAr Deadband 1
B0C4
IEC 61850 MMXU TotVA Deadband 1
B0C6
IEC 61850 MMXU TotPF Deadband 1
B0C8
IEC 61850 MMXU Hz Deadband 1
B0CA
IEC 61850 MMXU PPV.phsAB Deadband 1
B0CC
IEC 61850 MMXU PPV.phsBC Deadband 1
B0CE
IEC 61850 MMXU PPV.phsCA Deadband 1
B0D0
IEC 61850 MMXU PhV.phsA Deadband 1
B0D2
IEC 61850 MMXU PhV.phsB Deadband 1
B0D4
IEC 61850 MMXU PhV.phsC Deadband 1
B-52
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
1 to 60
s
1
0 to 1
---
1
---
---
---
0 to 1
---
1
---
---
---
---
---
---
---
---
---
0 to 7
---
1
0 to 4095
---
1
0 to 16383
---
1
0 to 1
---
1
1 to 65535
---
1
---
---
---
---
---
---
0 to 65534
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0.001 to 100
%
0.001
0.001 to 100
%
0.001
0.001 to 100
%
0.001
0.001 to 100
%
0.001
0.001 to 100
%
0.001
0.001 to 100
%
0.001
0.001 to 100
%
0.001
0.001 to 100
%
0.001
0.001 to 100
%
0.001
0.001 to 100
%
0.001
0.001 to 100
%
0.001
APPENDIX B
FORMAT
DEFAULT
F001
60
F102
1 (Enabled)
F209
"GSSEOut"
F102
0 (Disabled)
F072
0
F209
"GOOSEOut"
F072
0
F001
4
F001
0
F001
0
F001
0
F001
102
F213
"IEDName"
F213
"LDInst"
F204
"Location"
F102
0 (Disabled)
F102
0 (Disabled)
F001
0
F003
10000
F003
10000
F003
10000
F003
10000
F003
10000
F003
10000
F003
10000
F003
10000
F003
10000
F003
10000
F003
10000
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents