5.2 PRODUCT SETUP
5
5-18
DNP CURRENT SCALE
MESSAGE
FACTOR: 1
DNP VOLTAGE SCALE
MESSAGE
FACTOR: 1
DNP POWER SCALE
MESSAGE
FACTOR: 1
DNP ENERGY SCALE
MESSAGE
FACTOR: 1
DNP PF SCALE
MESSAGE
FACTOR: 1
DNP OTHER SCALE
MESSAGE
FACTOR: 1
DNP CURRENT DEFAULT
MESSAGE
DEADBAND: 30000
DNP VOLTAGE DEFAULT
MESSAGE
DEADBAND: 30000
DNP POWER DEFAULT
MESSAGE
DEADBAND: 30000
DNP ENERGY DEFAULT
MESSAGE
DEADBAND: 30000
DNP PF DEFAULT
MESSAGE
DEADBAND: 30000
DNP OTHER DEFAULT
MESSAGE
DEADBAND: 30000
DNP TIME SYNC IIN
MESSAGE
PERIOD: 1440 min
DNP MESSAGE FRAGMENT
MESSAGE
SIZE: 240
DNP OBJECT 1
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 2
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 20
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 21
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 22
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 23
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 30
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 32
MESSAGE
DEFAULT VARIATION: 1
N60 Network Stability and Synchrophasor Measurement System
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 1 to 10080 min. in steps of 1
Range: 30 to 2048 in steps of 1
Range: 1, 2
Range: 1, 2
Range: 1, 2, 5, 6
Range: 1, 2, 9, 10
Range: 1, 2, 5, 6
Range: 1, 2, 5, 6
Range: 1, 2, 3, 4, 5
Range: 1, 2, 3, 4, 5, 7