GE N60 Instruction Manual page 359

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

6 ACTUAL VALUES
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The metered values for real, reactive, and apparent power, as well as power factor, are displayed in this menu. The "SRC
1" text is replaced by whatever name was programmed by the user for the associated source (see

).
SETUP
SIGNAL SOURCES
When VTs are configured in wye, the N60 calculates power in each phase and three-phase power is measured as
When VTs are configured in delta, the N60 does not calculate power in each phase and three-phase power is measured as
where
S is the apparent power
V
, V
, V
, I
, I
, I
are phase voltage and phase current phasors
A
B
C
A
B
C
V
and V
are phase-to-phase voltage phasors
AB
CB
Î is the conjugate of I
g) ENERGY METERING

PATH: ACTUAL VALUES
METERING
 ENERGY
 SRC 1
MESSAGE
MESSAGE
MESSAGE
The metered values for real and reactive energy are displayed in this menu. The "SRC 1" text will be replaced by whatever
name was programmed by the user for the associated source (see
Because energy values are accumulated, these values should be recorded and then reset immediately prior to changing
CT or VT characteristics.
h) DEMAND METERING

PATH: ACTUAL VALUES
METERING
 DEMAND
 SRC 1
MESSAGE
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
SRC 1
APPARENT PWR
φc:
0.000
VA
SRC 1
POWER FACTOR
3φ:
1.000
SRC 1
POWER FACTOR
φa:
1.000
SRC 1
POWER FACTOR
φb:
1.000
SRC 1
POWER FACTOR
φc:
1.000
S = V
x Î
+ V
x Î
+ V
A
A
B
B
C
S = V
x Î
+ V
x Î
AB
A
CB

SOURCE SRC 1
ENERGY
SRC 1
POS WATTHOUR:
0.000
Wh
SRC 1
NEG WATTHOUR:
0.000
Wh
SRC 1
POS VARHOUR:
0.000
varh
SRC 1
NEG VARHOUR:
0.000
varh

SOURCE SRC 1
DEMAND
SRC 1
DMD IA:
0.000
A
SRC 1
DMD IA MAX:
0.000
A
x Î
C
C

SETTINGS
SYSTEM SETUP
6.3 METERING

SETTINGS
SYSTEM
(EQ 6.1)
(EQ 6.2)
6

).
SIGNAL SOURCES
6-17