GE N60 Instruction Manual page 236

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5.5 FLEXLOGIC™
Table 5–8: N60 FLEXLOGIC™ OPERANDS (Sheet 7 of 7)
OPERAND TYPE
OPERAND SYNTAX
PASSWORD
ACCESS LOC SETG OFF
SECURITY
ACCESS LOC SETG ON
ACCESS LOC CMND OFF
ACCESS LOC CMND ON
ACCESS REM SETG OFF
ACCESS REM SETG ON
ACCESS REM CMND OFF
ACCESS REM CMND ON
UNAUTHORIZED ACCESS
REMOTE DEVICES
REMOTE DEVICE 1 On
REMOTE DEVICE 2 On
REMOTE DEVICE 3 On
REMOTE DEVICE 16 On
REMOTE DEVICE 1 Off
REMOTE DEVICE 2 Off
REMOTE DEVICE 3 Off
REMOTE DEVICE 16 Off
RESETTING
RESET OP
RESET OP (COMMS)
RESET OP (OPERAND)
RESET OP (PUSHBUTTON)
SELF-
ANY MAJOR ERROR
DIAGNOSTICS
ANY MINOR ERROR
ANY SELF-TESTS
BATTERY FAIL
5
DIRECT DEVICE OFF
DIRECT RING BREAK
EQUIPMENT MISMATCH
ETHERNET SWITCH FAIL
FLEXLOGIC ERR TOKEN
IRIG-B FAILURE
LATCHING OUT ERROR
MAINTENANCE ALERT
PORT 1 OFFLINE
PORT 2 OFFLINE
PORT 3 OFFLINE
PORT 4 OFFLINE
PORT 5 OFFLINE
PORT 6 OFFLINE
PRI ETHERNET FAIL
PROCESS BUS FAILURE
REMOTE DEVICE OFF
RRTD COMM FAIL
SEC ETHERNET FAIL
SNTP FAILURE
SYSTEM EXCEPTION
TEMP MONITOR
UNIT NOT PROGRAMMED
TEMPERATURE
TEMP MONITOR
MONITOR
USER-
PUSHBUTTON 1 ON
PROGRAMMABLE
PUSHBUTTON 1 OFF
PUSHBUTTONS
ANY PB ON
PUSHBUTTON 2 to 12
Some operands can be re-named by the user. These are the names of the breakers in the breaker control feature, the ID
(identification) of contact inputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name
or ID of any of these operands, the assigned name will appear in the relay list of operands. The default names are shown in
the FlexLogic™ operands table above.
The characteristics of the logic gates are tabulated below, and the operators available in FlexLogic™ are listed in the Flex-
Logic™ operators table.
5-106
OPERAND DESCRIPTION
Asserted when local setting access is disabled
Asserted when local setting access is enabled
Asserted when local command access is disabled
Asserted when local command access is enabled
Asserted when remote setting access is disabled
Asserted when remote setting access is enabled
Asserted when remote command access is disabled
Asserted when remote command access is enabled
Asserted when a password entry fails while accessing a password protected
level of the N60
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Reset command is operated (set by all three operands below)
Communications source of the reset command
Operand (assigned in the
of the reset command
Reset key (pushbutton) source of the reset command
Any of the major self-test errors generated (major error)
Any of the minor self-test errors generated (minor error)
Any self-test errors generated (generic, any error)
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
See description in Chapter 7: Commands and targets
Asserted while the ambient temperature is greater than the maximum
operating temperature (80°C)
Pushbutton number 1 is in the "On" position
Pushbutton number 1 is in the "Off" position
Any of twelve pushbuttons is in the "On" position
Same set of operands as PUSHBUTTON 1
N60 Network Stability and Synchrophasor Measurement System
INPUTS/OUTPUTS
5 SETTINGS

RESETTING
menu) source
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents