GE N60 Instruction Manual page 462

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 32 of 62)
ADDR
REGISTER NAME
7E11
Underfrequency 1 Block
7E12
Underfrequency 1 Minimum Current
7E13
Underfrequency 1 Pickup
7E14
Underfrequency 1 Pickup Delay
7E15
Underfrequency 1 Reset Delay
B
7E16
Underfrequency 1 Source
7E17
Underfrequency 1 Events
7E18
Underfrequency 1 Target
7E19
Underfrequency 1 Reserved (8 items)
7E21
...Repeated for Underfrequency 2
7E32
...Repeated for Underfrequency 3
7E43
...Repeated for Underfrequency 4
7E54
...Repeated for Underfrequency 5
7E65
...Repeated for Underfrequency 6
Frequency (Read Only)
8000
Tracking Frequency
Generic Comparator Settings (Read/Write Setting) (6 modules)
8010
Comparator 1 Function
8011
Comparator 1 Addition/Subtraction Mode Operand
8012
Comparator 1 Scale Factor
8013
Comparator 1 Block
8014
Comparator 1 Target
8015
Comparator 1 Events
8016
Comparator 1 Argument A Bits (8 items)
801E
Comparator 1 Input Mode
801F
Comparator 1 Direction Mode
8020
Comparator 1 Pickup
8022
Comparator 1 Hysteresis
8024
Comparator 1 Pickup Delay
8025
Comparator 1 Reset Delay
8026
Comparator 1 Argument B Bits (8 items)
802C
Reserved (4 items)
8030
...Repeated for Comparator 2
8050
...Repeated for Comparator 3
8070
...Repeated for Comparator 4
8090
...Repeated for Comparator 5
80B0
...Repeated for Comparator 6
Generic Comparator Actual Values (Read Only) (6 modules)
8100
Comparator 1 Argument A Value
8102
Comparator 1 Argument B Value
8104
Comparator 1 Output Value
8106
...Repeated for Comparator 2
810C
...Repeated for Comparator 3
8112
...Repeated for Comparator 4
8118
...Repeated for Comparator 5
811E
...Repeated for Comparator 6
Direct Analog Input Actual Values (Read Only) (32 modules)
8180
Direct Analog Input 1 Value
8182
Direct Analog Input 2 Value
8184
Direct Analog Input 3 Value
8186
Direct Analog Input 4 Value
8188
Direct Analog Input 5 Value
818A
Direct Analog Input 6 Value
818C
Direct Analog Input 7 Value
B-40
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
0 to 65535
---
0.1 to 1.25
pu
20 to 65
Hz
0 to 65.535
s
0.001
0 to 65.535
s
0.001
0 to 5
---
0 to 1
---
0 to 2
---
0 to 1
---
2 to 90
Hz
0 to 1
---
0 to 65535
---
0.01 to 100
---
0 to 65535
---
0 to 2
---
0 to 1
---
0 to 65535
---
0 to 1
---
0 to 1
---
-25400 to 25400
---
0 to 5000
---
0 to 65.353
s
0.001
0 to 65.353
s
0.001
0 to 65535
---
0 to 65535
---
-12700 to 12700
---
-12700 to 12700
---
-25400 to 25400
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
APPENDIX B
FORMAT
DEFAULT
1
F300
0
0.01
F001
10
0.01
F001
5950
F001
2000
F001
2000
1
F167
0 (SRC 1)
1
F102
0 (Disabled)
1
F109
0 (Self-reset)
1
F001
0
0.01
F001
0
1
F102
0 (Disabled)
1
F300
0
0.01
F001
100
1
F300
0
1
F109
0 (Self-reset)
1
F102
0 (Disabled)
1
F300
0
1
F515
0 (SIGNED)
1
F517
0 (OVER)
0.01
F004
1000000
0.01
F003
50000
F001
0
F001
0
1
F300
0
1
F001
0
0.01
F004
0
0.01
F004
0
0.01
F004
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents