5.7 CONTROL ELEMENTS
In the above equations,
∆t is the power cycle duration.
n is the power cycle index.
t
is the trip time calculated at index n as per the IEC255-8 cold curve or hot curve equations.
op(In)
t
is the reset time calculated at index n as per the reset time equation.
rst(In)
I
is the measured overload RMS current at index n.
n
E
is the accumulated energy at index n.
n
E
is the accumulated energy at index n – 1.
n – 1
The thermal overload protection element removes the
emergency, the thermal memory and
All calculations are performed per phase. If the accumulated energy reaches value 1 in any phase, the thermal overload
protection element operates and only resets when energy is less than 0.05 in all three phases.
Table 5–12: TYPICAL TIME CONSTANTS
PROTECTED EQUIPMENT
Capacitor bank
Overhead line
Air-core reactor
5
Busbar
Underground cable
The logic for the thermal overload protection element is shown below.
5-166
E
E
=
n
THERMAL PROT 1 OP
TIME CONSTANT
MINIMUM RESET TIME
10 minutes
30 minutes
10 minutes
20 minutes
40 minutes
30 minutes
60 minutes
20 minutes
20 to 60 minutes
60 minutes
Figure 5–76: THERMAL OVERLOAD PROTECTION SCHEME LOGIC
N60 Network Stability and Synchrophasor Measurement System
t Δ
-------------- -
n 1
t
rst In
(
)
output operand when E < 0.05. In case of
THERMAL PROT 1 OP
output operand can be reset using
5 SETTINGS
(EQ 5.17)
setting.
THERM PROT 1 RESET