Diagnostics
Diagnostics Overview:
Screen Buttons:
Diagnostics Menu
HW Reset
Restart
WalkTest
Cfig
Earth Fault
Earth Fault
Download
Search
HW Reset:
Tap the Hardware Reset button to re-initialize the state of certain hardware components. A hardware reset is typically
used to reset a Class A Trouble after the problem causing the Trouble is resolved.
Note: If you attempt to perform a hardware reset without first fixing the problem causing the Trouble, the hardware reset fails and the
Trouble re-appears.
Restart:
Restart Menu
WarmStart
ColdStart
WalkTest:
WalkTest Settings
Next
Group
Walktest Group
Information
Prev
Group
Select Item
Use the Diagnostics function to run tests on the panel and the devices. Refer to Figure 6
for access levels required for each option inside the Diagnostics screen.
Scroll Up
Scroll down
Date
Time
Piezo
USER
Silence
BUTTON 1
USER
NAC
BUTTON 2
Latch
Miswire Test
USER
BUTTON 3
Next Page
Figure 12. Diagnostics Screen
Tap the Restart button to restart the panel by Warm Start or Cold
Date
Time
Start:
USER
• Warm Start: Preserves the logs and the disabled status of any
BUTTON 1
USER
BUTTON 2
• Cold Start: Clears all history logs and re-enables any points
USER
BUTTON 3
Tap the WalkTest button to open the WalkTest Settings screen,
Date
which contains Walktest groups configured by technicians for use
Time
during maintenance testing. The following functions are available:
• Tap the Next Group button to select the next WalkTest group.
• Tap the Prev Group button to select the previous WalkTest
• With an item in the WalkTest group selected, tap the Select
Item button to open a new screen where information and
additional functions for that item are available.
23
4007ES Operator's Manual (579-1165)
Accept
Diagnostics Menu
Duplicate
Weak Answer
Search
Device Search
CO
Install
Algorithms
Mode
points that are in disabled state.
that were previously disabled.
group.
Return
Date
Time
TrueAlert
TrueAlert
USER
Test
NAC Test
BUTTON 1
USER
Net Diag
BUTTON 2
USER
BUTTON 3
Previous Page
Continued on next page
Need help?