Simplex 4007ES Operator's Manual page 11

Hide thumbs Also See for 4007ES:
Table of Contents

Advertisement

Supervisory and Trouble Conditions, Continued
Processing Supervisory and
Trouble Conditions:
Global Acknowledge
Tap the ACK button.
Individual Acknowledge
Tap the unacknowledged Trouble from the events list.
Note: The Troubles that have not been acknowledged display the text "Press to acknowledge" on the top right of the button.
When a Supervisory or a Trouble event occurs, it needs to be acknowledged and the
cause of the event resolved for the system to return to normal. Two types of
acknowledging modes can be configured on the panel.
1. Global Acknowledge
All the zones inside the Zone Supervisory or Zone Trouble lists are acknowledged at
once.
2. Individual Acknowledge
Each zone inside the Zone Alarm List are acknowledged separately.
Note: A zone groups multiple points together and the Zone Supervisory or Zone Trouble list
displays all the zones where Trouble or Supervisory conditions occurred.
Trouble in System
Most Recent of 5
SYSTEM TIME/DATE INVALID OR NOT SET
ABNORMAL
First of 5
CARD 1, NAC POWER SUPPLY
NAC MISWIRE
TROUBLE
ACK
Alarm Functions
5
Trouble in System
Most Recent of 5
SYSTEM TIME/DATE INVALID OR NOT SET
ABNORMAL
First of 5
CARD 1, NAC POWER SUPPLY
NAC MISWIRE
TROUBLE
ACK
Alarm Functions
5
11
4007ES Operator's Manual (579-1165)
Date
Time
Date
Date
Menu
Date
Time
Press to acknowledge
Press to acknowledge
Menu

Hide quick links: