Disable / Re-Enable Alarm Devices (H2/B9) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
25.9
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B9
"A"
"A"
"Return"
"Return"
Rev: -

Disable / re-enable alarm devices (H2/B9)

Disabled alarm devices are listed in menu H4/U1.
Outputs for alarm devices can be collectively disabled and re-enabled
via this menu. Disabled output will stay disabled, until re-enabled
again via this menu.
When all outputs type Alarm devices have been disabled, the LEDs
"Disablements" (L8) and "Fault / Disablements Alarm devices"
(L13) will be turned ON.
When all outputs type Alarm devices have been re-enabled, the LED
"Fault / Disablements Alarm devices" (L13) will be turned OFF.
NOTE! This function for alarm devices is not the same as for push
button "Silence alarm devices" (P3) – unless the option Button
"Silence alarm devices" disables alarm devices, is selected in EBLwin
System properties, see chapter "Silence Alarm devices", page 29.
This menu has higher priority than the push button "Silence alarm
devices".
Text in display
Disable or re-enable
Disable zone
Disable / re-enable alarm devices
Alarm devices in normal condition
Press ACCEPT to disable
Alarm devices disabled
Press ACCEPT to re-enable
Disable or re-enable outputs for
routing equipment
Disable or re-enable
EBL128 Operating Instructions V2.0.x
ACCEPT? H2
ACCEPT? B1
ACCEPT?
ACCEPT?
ACCEPT? H2
96
Comments
According to chapter
"Access", see page 81.
B9
Depending on the actual
status one of the texts will
be shown.
Scroll or press "Return" to
B9
return to H2.
Scroll or press "Return".