Door Open; Led "Door Open; Outputs For Routing Equipment (Fire Brigade Tx And Fault Tx); Silence Buzzer - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
Rev: -
14
14.1
14.2
14.3

Door open

A special key is used to open the EBL128 door to get access to the
front, see chapter "User level, User name & Password", page 23. The
same type of key is also used to open the ext. FBP door / the key
31
switch. Door open
is indicated by LED "Door open" (L10).

LED "Door open"

Valid for the door in EBL128 or an external FBP connected to
EBL128: Door open in EBL128 is indicated by LED "Door open" in
EBL128. Door open in an ext. FBP is indicated by LED "Door open"
in EBL128.
Outputs for routing equipment (Fire
brigade tx and Fault tx)
In EBLWin the following can be programmed:
None: The output(s) for routing equipment (Fire brigade and fault tx)
will not be disabled by any open door.
Any Control Unit Door: Door open in EBL128 will disable the
output(s) for routing equipment (Fire brigade and fault tx).
Any Door: Door open in EBL128 and/or Ext. Fire Brigade Panel will
disable the output(s) for routing equipment (Fire brigade and fault
tx).
Disabled outputs for routing equipment are indicated by the LED
"Disablements" (L8) and "Fault / Disablements Fire brigade tx"
(L15) and listed in menu H4/U1.
In the display is shown:
All outputs to fire alarm routing equip.
disabled by open door

Silence buzzer

In EBLWin the following can be programmed:
The buzzer in the control unit will be turned off as long as the
EBL128 door is open.
(This function is a violation to the EN54-2 standard.)
31
In the ext. FBP 1828: when the key is turned to the "position open /
access".
39
EBL128 Operating Instructions V2.0.x

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents