Panasonic Eco Solutions Nordic AB
MEW01623
Rev: -
21.2
21.3
indicating that EBL128 is in the so called "Boot mode". LEDs
"Alarms queued" (L2) are indicating the Flash memory
programming. When the download is completed, LEDs "Alarms
queued" (L2) will be turned off and the control unit has to be
restarted. NOTE! First pull off the jumper "JP2" (BOOT)!
8. LED "Operation" (L6) will be lit.
9. There will be at least a "restart fault" (see chapter "Restart", page
77), i.e. LEDs "General fault" (L7) and "Fault tx activated" (L11)
will be lit. Acknowledge all faults (menu H6).
10. New Site Specific Data (SSD)

Earlier S/W version download

For some reason it might be required to "downgrade" to an earlier
S/W version. The download procedure is the same as for a new S/W.
NOTE! A corresponding Win128 / EBLWin version has to be used.
EBL128 version N.N.x with Win128 / EBLWin version N.N.x.

S/W download in Display Units

New S/W for the 1728, 1735 / 1736 & 1826 / 1828 units can also be
downloaded via EBLWin. The PC has to be connected to the RS232
connector "J2" in the unit respectively.
See the "Technical Description" for the unit respectively.
64
Old SSD can be opened in EBLWin, saved and then downloaded as new
SSD.