Test Of Alarm Devices (H8/S6) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
31.6
Action
"Access"
Scroll to menu H8.
"A"
Scroll to menu S6.
"A"
"A"
"A"
"Return"
"Return"
Rev: -

Test of alarm devices (H8/S6)

The programmable outputs
collectively activated via this sub menu (S6), which makes it possible
to test the alarm devices without too much disturbance on site.
The test cannot be started if fire alarm is already activated in EBL128.
When the test starts, the alarm devices will sound for approx. 1
second, be silent for approx. 29 seconds, sound for approx. 1 second
86
and so on.
NOTE! Also disabled (and silenced) alarm devices will be tested.
Text in display
Maintenance
Acknowledge SERVICE signal
Test of alarm devices
Test of alarm devices?
Test of alarm devices in progress.
End test?
Test of alarm devices?
Test of alarm devices
Maintenance
85
Including Addressable siren 3377 / 4477, Addressable sounder base 3379,
Addressable beacon 4380 and Light indicator 4383.
86
The output activation will be steady (continuous). For the alarm devices
3377 / 4477 and 3379, the tone with the highest priority level (and type
"alarm device") will be automatically selected.
EBL128 Operating Instructions V2.0.x
85
of type "Alarm device" can be
ACCEPT? H8
ACCEPT? S1
ACCEPT? S6
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? S6
ACCEPT? H8
131
Comments
According to chapter
"Access", see page 81.
Press "A" to start the test.
The test will now
continue until stopped
via this menu (S6) or
automatically after one
hour or if a fire alarm is
activated.
Press "A" to stop the test.
Scroll or press "Return" to
return to menu H8.
Scroll or press "Return"