16.4.2
16.4.2.1
16.5
16.6
This alarm will also generate a fault message, see chapter "Key
cabinet alarm reset", page 55. It is indicated by LED "General fault"
(L7) and the "Fault tx" output(s) will be activated.

Key cabinet opened in conjunction with a fire alarm

The fire brigade personnel can open the key cabinet if a fire alarm
already is activated in EBL128 In this case there will be no key
cabinet alarm or fault generated when the key cabinet is opened.
Restoring the key after a fire alarm
When all fire alarms are reset (see chapter "Alarm reset", page 53),
the key has to be restored in the key cabinet within 5 minutes. If not,
a fault will be generated, see chapter "Key cabinet alarm reset", page
55.

Quiet alarm

One or more smoke detectors, programmed for quiet alarm, e.g. used
for fan control (stop / start depending on the type of fan), have passed
the fire alarm level.
Quiet alarm is normally used in conjunction with a Fan control panel
49
(4593).
Indications and actions:
LEDs "Fire" (L1) are blinking (0.4 / 0.4 sec.), the buzzer sounds (0.8 /
5 sec.) and there is a Quiet alarm presentation in the display:
Quiet alarm detector ZZ/AA
(user definable text message)
Programmable outputs for quiet alarm are activated, e.g. 3361 outputs
controlling supply air fans and standard fans, i.e. any output with a
control expression containing the trigger conditions "Quiet Alarm
Zone" or "Quiet Alarm Zone Address".

Alarm Acknowledgement Facility (AAF)

Used on the Australian market only.
One or more Alarm Acknowledgement Facility Controls
the system.
During the Acknowledgement Period (10-60 sec.) there is an
indication in the control unit display:
49
The Fan control panel can be used for control of 4 + 4 fans. For each
group of four fans is also one I/O Matrix board 4582 required and for each
fan is one I/O unit 3361 required.
50
The AAF Control is available on the Australian market only.
51
EBL128 Operating Instructions V2.0.x
50
are used in