Panasonic Eco Solutions Nordic AB
MEW01623
28.2
Action
"Access"
Scroll to menu H5.
"A"
Scroll to menu A2
"A"
"Return"
"Return"
Rev: -

Sensitive fault detection mode (H5/A2)

"Sensitive fault detection mode" means that the normal time delays for
all type of faults are reduced, which makes it possible to find faults
during the commissioning instead of later.
This mode is indicated by the LED "Fault tx activated" (L11).
NOTE 1!
The "Fault" output for routing equipment is also
"activated".
NOTE 2! Don't forget to turn this mode off after the commissioning.
Text in display
Service
Calibration of supervised outputs
Sensitive fault detection mode
Sensitive fault detection mode is
not active.
Press ACCEPT to activate
Sensitive fault detection mode is active
Press ACCEPT to deactivate
Sensitive fault detection mode
Service
NOTE! Don't forget to turn this mode off after the commissioning.
EBL128 Operating Instructions V2.0.x
ACCEPT? H5
ACCEPT? A1
ACCEPT? A2
ACCEPT? A2
ACCEPT? H5
114
Comments
According to chapter
"Access", see page 81.
Depending on the actual
status one of the texts will be
shown.
Press "A" to accept or press
"Return" to menu A2.
Scroll or press "Return" to
H5.
Scroll or press "Return".