Disable All Control, Ventilation, Exting Or Interlocking Outputs (H2/B4) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
25.4
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B4.
"A"
"0", "1", "2" or "3"
"A"
Depending on the
chosen type the
following will be
shown:
"A"
"Return"
"Return"
Rev: -
Disable all control, ventilation, exting or
interlocking outputs (H2/B4)
Outputs programmed as type Control (general), type Fire ventilation,
type Extinguishing system and type Interlocking can for the type
respectively be collectively disabled (all at the same time). Disabled
output means that even if the control expression (trigger condition)
for the output respectively is fulfilled (true), the output will not be
activated. Disabled outputs are shown in menu H4/U1.
The outputs will be disabled until re-enabled again (via H2/B8).
Text in display
Disable or re-enable
Disable zone
Disable all control, ventilation, exting
or interlocking outputs
Disable type:0
2=Exting 3=Interlocking
All xxxxxxx outputs disabled
Disable type:0
2=Exting 3=Interlocking
Disable all control, ventilation, exting
or interlocking outputs
Disable or re-enable
EBL128 Operating Instructions V2.0.x
ACCEPT? H2
ACCEPT? B1
ACCEPT?
0=Control 1=Ventilation
ACCEPT?
0=Control 1=Ventilation
ACCEPT?
ACCEPT?
ACCEPT? H2
90
Comments
According to chapter
"Access", see page 81.
B4
For the type respectively
press:
"0"=control outputs
"1"=ventilation outputs
"2"=extinguishing outputs
"3"=interlocking outputs
Press "A" to accept.
LED "Disablements" (L8)
will light up.
xxxxx=control, ventilation,
extinguishing or
interlocking
If more disablements shall
be done, continue like
above. If not, press
"Return" to menu B4.
Scroll or press "Return" to
B4
menu H2.
Scroll or press "Return".