When the outputs are disabled in the c.i.e. via menu H2/B4 it is not
possible to re-enable them from the FBF (via button "Brandfall
Steuerungen ab").

Indication "Brandfall Steuerungen ab"

The indication "Brandfall Steuerungen ab" on "Feuerwehr-
Bedienfeld" (FBF) is turned on if any of the three output types
Control, Fire ventilation and Extinguishing is disabled.

Button "Akustische Signale ab"

The button "Akustische Signale ab" on "Feuerwehr-Bedienfeld" (FBF)
has the same function as the menu "Disable alarm devices" (H2/B9) in
the c.i.e.
If pushed during fire alarm condition the button "Akustische Signale
ab" will also silence the buzzer in the c.i.e.
When the outputs are disabled from the FBF (via button "Akustische
Signale ab") it is not possible to re-enable them from the CIE.
However, during fire alarm condition and if the outputs to fire alarm
devices (outputs C) have been disabled from the c.i.e. it is possible to
re-enable them from the FBF.

Indication "Akustische Signale ab"

The indication "Akustische Signale ab" on "Feuerwehr-Bedienfeld"
(FBF) is turned on when the outputs to alarm devices are disabled.

Indication in button "Akustische Signale ab"

(Switch "1" on the DIP switch in FBF (2003) shall be in position ON.)
The LED in button "Akustische Signale ab" follow the indication
"Akustische Signale ab" on "Feuerwehr-Bedienfeld" (FBF) i.e. LED
turned on means that the outputs to alarm devices are disabled.

The buzzer in the c.i.e.

Even if the outputs to alarm devices are disabled, the buzzer in the
c.i.e. will re-sound in case of a new alarm. It is possible to silence the
buzzer by pressing the button "Akustische Signale ab" (outputs to
alarm devices will be re-enabled) and immediately press the button
"Akustische Signale ab" again (outputs to alarm devices will be
disabled again). In this case there is a risk that the alarm devices
will sound for a short while.
Button "ÜE ab"
The button "ÜE ab" on "Feuerwehr-Bedienfeld" (FBF) will disable all
the outputs of type Routing equipment, nominated as output E in DIN
EN 54-1.