Touch Screen; Alarm Presentation; Control Panel; Usb - Panasonic 2000 Manual

Control and indicating equipment eblone
Table of Contents

Advertisement

2000 - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION

3.2. TOUCH SCREEN

The display is a colour touch screen.
Data:
Display size: 7.0"
TFT Screen LCD type
Capacitive display
Resolution: 1024 x 600 RGB
There are 12 status LEDs integrated in the display module:
Fire
Fire brigade tx activated
Fire protection equipment activated
Evacuation activated
Operation
In case of no fire alarms, faults, disablements or test condition, the touch screen will go into sleep mode after 2 minutes.

3.3. ALARM PRESENTATION

In case of fire alarms the fire brigade personnel are able to see which alarm point/points having activated fire alarm and to take
required operating control of the system.
The information displayed in the upper part is depending on how many alarm points having activated fire alarm. In the middle part
will the fire alarms be shown, one alarm point together with an user definable alarm text (if programmed).

3.4. CONTROL PANEL

The touch screen is also used for CIE operations such as commissioning, monthly test and maintenance. To get access to operate
the CIE, a user name and password is required. Up to ten user names can be used for three different user level types.
A password (six digits) for each user name is required.
See EBLOne Operating instructions for more information about status LEDs, alarm presentation and the control panel.

3.5. USB

The CIE is equipped with an USB interface (Type C), used for PC connection.
Test Mode
Fire brigade tx delay
System Fault
Fault
Disablement
Alarm device
Fault/Disablement
Fire brigade tx
Fault/Disablement
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

2000k

Table of Contents