Disable output (H2/B3)

Up to 100 Control outputs, except outputs of type "alarm device",
can be individually disabled. Disabled output will stay in (or return
to) the normal condition for the output respectively.
Text in display
Disable or re-enable
Disable zone
Disable output
Disable output type: 0
0=Loopunit 1=S 2=R0 3=EXPB
Disable output 0 technical address 000
Disable S0
Disable R0
Disable output 0 expansion board 0
Output R0 disabled
Disable R0
Disable output type: 0
0=Loop unit 1=S 2=R0 3=EXPB
72
Expansion board (EXPB) 0-3,
4581: Relay output 0-7 alt. 4583: Output 0-2.
EBL128 Operating Instructions V2.0.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B3
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
88
Comments
According to chapter
"Access", see page 81.
Press:
"0"=3361 or 3377/4477
or 3379 or 3364 or 4380
or 4383
"1"=C.i.e. output S0-S1
"2"=C.i.e. output R0
"3"=C.i.e. exp. board
72
output.
Press "A" to accept.
Regarding the 3377/4477
& 3379 units' output no.:
0=high priority
1=medium priority
2=low priority
Write the data.
Press "A" to accept.
LED "Disablements"
(L8) will light up.
If more disablements
shall be done, continue