Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x
Commissioning of a new unit / SSD
download
The cable (RS485 line) to the AA unit(s)
connection diagram for the system respectively.
In the EBL512 c.i.e. the 1587 board shall be mounted. Remove the
fuse "F1" on the 1587 board.
The EBL128 c.i.e. shall be powerless and the "RS485 transceiver
component 4552" shall be plugged on the main board (4556).
On the EBL512 G3 main board (5010) remove the fuse "F19".
The SW mode and the address have to be set in each new unit
according to chapter "SW mode & Address setting", page 16. Here
follows a brief summary (a recommended sequence of actions):
1. Connect the cable from the c.i.e. to the AA unit 's terminal
block "J1".
2. When all connections are done put back the fuse "F1" on the
1587 board in the EBL512 c.i.e. / power up the EBL128 c.i.e.
/ put back the fuse "F19" on the main board (5010) in the
EBL512 G3 c.i.e., i.e. the AA unit(s) will now be powered up.
3. A brand new unit will automatically be ready for the SW mode
setting.
4. After SW mode and address setting press "P2" (yellow) and the
unit will restart, see chapter "Restart", page 23.
5. Since the SSD is not downloaded in the c.i.e. there will be a
fault message in the unit's display:
"No contact with Control unit".
All LED:s in the unit will be turned off.
6. Now the SSD have to be downloaded via Win512 / Win128 /
24
Win512 G3.
Win128 / Win512 G3 download SSD" dialog box, verify that
the "Download FBP / AAU" checkbox is marked. Start the
download of SSD.
7. When the download of SSD to the c.i.e. is finished, it will
restart. Then the download of SSD to the AA unit(s) will take
23
One or more ext. FBPs and/or Alert Annunciation Units can be connected.
24
Via Win512 is the 1587 board programmed. Via Win512 / Win128 /
Win512 G3 is each unit (e.g. an AA unit) programmed regarding Address,
Selective alarm presentation, if the buzzer should be disabled etc. When
required, also "User definable text messages" (alarm texts).
23
shall be connected. See
Connect the PC to the c.i.e. In the "Win512 /
21