18
P O W E R VA L U E 1 1T G 2 1 - 3 K VA B/ S
—
5 LCD settings
—
5 1 LCD setting overview
You can use the LCD module to access the
—
12 The LCD display panel
settings for each operating mode.
The available modes are displayed in the center
oval. Table 11 below shows the different display
name acronyms for each mode.
—
Table 11: LCD mode setting options
String Meaning
OPV
OPF
bYPA
MOdE
EbPN
bATT
CHG
Setting Options
Voltage options are:
• 220V
Output voltage
• 230V
• 240V
Frequency options are:
Output frequency
• 50Hz
• 60 Hz
• Select 000 for
Bypass Disable.
• Select 001 for
Bypass Enable.
• UPS will enter bypass mode
Bypass status
after several seconds if
Bypass Enable is selected.
• UPS will turn to no output
mode after several seconds
if Bypass Disable is selected.
• UPS—Normal operating
mode
Operating mode
• ECO—High-efficiency
mode
• CVF—Converter mode
• Values are 000 or 009.
External battery
• 009 means there are 9
pack number
external battery packs.
Battery time values are:
• 000—Battery remaining
time function is disabled
and will not display on LCD
in battery mode.
Battery remaining
• 001—Battery remaining
time
time function is enabled,
and the time will display
(minutes or seconds) in
battery mode or battery
test mode. bATT will
display on LCD every 2s.
• 3.0/6.0 for 1KL T
Charger current
(3.0 stands for 3A charger)
• 1.5/3.0/4.5/6.0 for 2KL/3KL T
5 1 1
Navigating the LCD
To access settings mode on the LCD display
panel, press the "Enter" button for more than
1 second.
—
12
The above modes are displayed individually in the
center oval. You can cycle through each mode by
pressing and holding "Enter" and then pressing
"Select."