P O W E R VA L U E 1 1T G 2 1 - 3 K VA B/ S

5 LCD settings

5 1 LCD setting overview

You can use the LCD module to access the
12 The LCD display panel
settings for each operating mode.
The available modes are displayed in the center
oval. Table 11 below shows the different display
name acronyms for each mode.

Table 11: LCD mode setting options

String Meaning
OPV
OPF
bYPA
MOdE
EbPN
bATT
CHG
Setting Options
Voltage options are:
• 220V
Output voltage
• 230V
• 240V
Frequency options are:
Output frequency
• 50Hz
• 60 Hz
• Select 000 for
Bypass Disable.
• Select 001 for
Bypass Enable.
• UPS will enter bypass mode
Bypass status
after several seconds if
Bypass Enable is selected.
• UPS will turn to no output
mode after several seconds
if Bypass Disable is selected.
• UPS—Normal operating
mode
Operating mode
• ECO—High-efficiency
mode
• CVF—Converter mode
• Values are 000 or 009.
External battery
• 009 means there are 9
pack number
external battery packs.
Battery time values are:
• 000—Battery remaining
time function is disabled
and will not display on LCD
in battery mode.
Battery remaining
• 001—Battery remaining
time
time function is enabled,
and the time will display
(minutes or seconds) in
battery mode or battery
test mode. bATT will
display on LCD every 2s.
• 3.0/6.0 for 1KL T
Charger current
(3.0 stands for 3A charger)
• 1.5/3.0/4.5/6.0 for 2KL/3KL T
5 1 1

Navigating the LCD

To access settings mode on the LCD display
panel, press the "Enter" button for more than
1 second.
12
The above modes are displayed individually in the
center oval. You can cycle through each mode by
pressing and holding "Enter" and then pressing
"Select."