Selection Of Outdoor Unit For Pressure Adjustment - Toshiba MMY-MAP0804HT8-E Service Manual

Multi type
Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

(5) [rd] [... FF] will be displayed on the 7-segment display, and pump-down operation will start.
* To put the operation on hold midway, turn off the power supply to all the outdoor units, or press SW05 on the
interface P.C. board.
If oil has degraded due to
compressor fault, undo SV3A
valve connector.
(6) Approx. 10 minutes after the system starts up, fully close the gas pipe service valve of the failed outdoor unit.
(7) Press SW04 of the failed outdoor unit to have pressure data (MPa) displayed.
(The display switches each time SW04 is pressed.)
Display Example

[Selection of outdoor unit for pressure adjustment]

(8) Of all outdoor units operating in the pump-down mode, select the one with the lowest unit No. as an outdoor
unit for pressure adjustment.
Identifying Unit No.
The unit No. is the number displayed on the 7-segment display when SW01/02/03 are set to 1/1/1.
([U#] [– – –]: # represents the unit No.)
[Setup of outdoor units other than unit for pressure adjustment and failed unit]
(9) Leaving the balance pipes of the unit for pressure adjustment and the failed unit fully open, fully close the
balance pipe service valves of all other outdoor units.
[Setup of outdoor unit for pressure adjustment]
(10)Set SW01/02/03 on the interface P.C. board of the outdoor unit for pressure adjustment to 1/2/2.
(11)As the low-pressure sensor output is displayed on the 7-segment display, adjust the pressure to around 0.12
MPa by slowly closing the gas pipe service valve, with checking pressure data.
(12)Compare the low-pressure sensor outputs of the failed unit with that of the unit for pressure adjustment, and
wait until the two pressure readings become almost the same. After letting the system continue operating for
a while longer, fully close the gas pipe service valve of the unit for pressure adjustment.
Downloaded from
www.Manualslib.com
Header unit
(3)
(4) Set SW01/02/03 to 2/11/1.
[rd] [... ... ...] is displayed.
p
Press SW04 and hold for 5 seconds or more.
(5) [rd] [ FF] is displayed (pump-down operation starts).
Behavior during pump-down operation
Outdoor unit
Behavior
Compressors: Turned off
Outdoor fan: On
Failed outdoor unit
PMV1, PMV2 and PMV4: Open
SV2/3A/3B/3C/3D/3E/3F: On
SV41/42/43/5/6: On
Operates in test cooling
Every other outdoor unit
operation mode
[rd] [...11]
Initial display
High-pressure sensor output
manuals search engine
Failed outdoor unit
Interface P.C. board of failed outdoor unit
[Pd] [1.20]
Low-pressure sensor output
249
(1)
Connect liquid pipe check joint and low
pressure-side check joint using charge
hose, and purge hose of air.
(2)
Fully close liquid pipe service valve.
(Leave service valves of gas and
balance pipes fully open.)
[Ps] [1.20]