BACKUP OPERATION
(EMERGENCY OPERATION)
This product offers backup modes of operation to tide over certain emergency situations. If a fault occurs in one of
the compressors, it is possible to operate the system on an emergency basis by operating only the remaining
compressor(s), (compressor backup operation).
If one of the outdoor units fails in a combined outdoor unit system, the system can be operated on an emergency
basis by keeping only the remaining outdoor unit(s), (outdoor unit backup operation).
Perform backup operation setting in accordance with the procedure described below.

9-1. Note for Backup Operation

The method of backup operation differs according to the contents of fault as shown in the table below.
One of the compressors in the same unit fails (see Note 1)
All the compressors in the same unit fail
A fault occurs in a compressor motor coil (e.g. a layer short-circuit)
A fault occurs in a refrigerating cycle part, fan or related part, or electrical part
A fault occurs in a temperature sensor or pressure sensor
Note 1: If the compressor has failed due to a fault in its motor coil (e.g. a layer short-circuit), do not preform
compressor backup operation because of severe oil degradation. It could damage other outdoor units.
Note 2: Keep the number of backed-up outdoor units under compressor backup operation to one in the system
(single refrigerant line). For a three-compressor model, the backing up of two faulty compressors is
prohibited.
Note 3: Keep the number of backed-up outdoor units under outdoor unit backup operation to one in the system
(single refrigerant line).
Note 4: It is prohibited to combine compressor backup operation and outdoor unit backup operation.
Note 5: With a two-outdoor unit system containing an MMY-
MAP1604 (or MAP1404 ) and an MMY-MAP1204 (or
MMY-MAP0804 or MAP1004 ), do not preform outdoor
unit backup operation to back up the MMY-MAP1604
(or MAP1404 ).
It could lead to compressor failure due to the abnormal
operation.
Downloaded from
www.Manualslib.com
Contents of fault
Backed-up compressor Backed-up compressor
Example
Prohibited
Example
Prohibited
Backed-up compressor
Example
Prohibited
manuals search engine
Method of backup operation
Compressor backup (see Note 2)
Outdoor unit backup or cooling-
season outdoor unit backup (see
Notes 1, 3, 4 and 5)
Two backed-up compressors
Example
Prohibited
Backed-up outdoor unit Backed-up outdoor unit
Faulty
Faulty
Backed-up outdoor unit
Faulty
Example
Prohibited
241
Setting procedure
Go to 9-2.
Go to 9-3. or 9-4.
Backed-up outdoor unit
Faulty
MMY-MAP1604∗
MMY-MAP1204∗
(MMY-MAP1404∗)
(MMY-MAP1004∗)
(MMY-MAP0804∗)