Toshiba MMY-MAP0804HT8-E Service Manual page 184

Multi type
Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

Outdoor 7-segment display
Main
remote
Check
controller
code
F29
F31
F31
H01
H01
H02
H02
H03
H03
H05
H05
H06
H06
*1 Total shutdown in case of header unit
Continued operation in case of follower unit
Downloaded from
www.Manualslib.com
Check code
Location
AI-NET central
of
control
detection
remote
Sub-code
controller
Indoor
12
unit
I/F
1C
01: Compressor 1
IPDU
side
02: Compressor 2
side
1F
03: Compressor 3
side
01: Compressor 1
IPDU
side
02: Compressor 2
side
03: Compressor 3
side
1d
01: Compressor 1
IPDU
side
02: Compressor 2
17
side
03: Compressor 3
side
I/F
I/F
20
manuals search engine
System
Error detection
Description
status
Other indoor
Stop of
Indoor P.C. board does not
error
corresponding
operate normally.
unit
Outdoor
All stop *1
Outdoor P.C. board (I/F)
EEPROM
does not operate normally.
error
Compressor
All stop
Inverter current detection
breakdown
circuit detects overcurrent
and shuts system down.
Compressor
All stop
Overcurrent is detected
error (lockup)
several seconds after
MG-CTT error
startup of inverter
compressor.
Current
All stop
Current flow of at least
detection
specified magnitude is
circuit error
detected despite inverter
compressor having been
shut turned off.
TD1 sensor
All stop
Discharge temperature of
miswiring
compressor 1 (TD1) does
(incomplete
not increase despite
insertion)
compressor being in
operation.
Activation of
All stop
Low-pressure Ps sensor
low-pressure
detects operating pressure
protection
lower than 0.02MPa.
183
Check items (locations)
condition(s)
• Check for defect in indoor P.C.
board (faulty EEPROM)
• Check power supply voltage.
• Check power supply noise.
• Check for defect in outdoor
P.C. board (I/F).
• Check power supply voltage.
(AC200V ± 10%).
• Check for defect in
compressor.
• Check for possible cause of
abnormal overloading.
• Check for defect in outdoor
P.C. board (A3-IPDU).
• Check for defect in
compressor.
• Check power supply voltage.
(AC200V ± 10%).
• Check compressor system
wiring, particularly for open
phase.
• Check connection of
connectors/terminals on A3-
IPDU P.C. board.
• Check conductivity of case
heater.
(Check for refrigerant
entrapment inside
compressor.)
• Check for defect in outdoor
P.C. board (A3-IPDU).
• Check outdoor MG-CTT.
• Check current detection circuit
wiring.
• Check defect in outdoor P.C.
board (A3-IPDU).
• Check installation of TD1
sensor.
• Check connection of TD1
sensor connector and wiring.
• Check resistance
characteristics of TD1 sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check service valves to
confirm full opening
(both gas and liquid sides).
• Check outdoor PMVs for
clogging (PMV1, 2).
• Check for defect in SV2 or SV4
circuits.
• Check for defect in low-
pressure Ps sensor.
• Check indoor filter for clogging.
• Check valve opening status of
indoor PMV.
• Check refrigerant piping for
clogging.
• Check operation of outdoor fan
(during heating).
• Check for insufficiency in
refrigerant quantity.
MG-CTT: Magnet contactor