Error/Operation Output; Output Relay (K1, K2, K3) Contact Specifications - Toshiba MMY-MAP0804HT8-E Service Manual

Multi type
Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

6-8-7. Error/Operation Output

Operation
In-operation output: An in-operation indication signal is output as long as at least one indoor unit is in operation in
the line.
Error output: An error indication signal is output if an error occurs in at least one indoor/outdoor unit in the line.
Note 1: Output Relay (K1, K2, K3) Contact Specifications
• Output terminals (OUTPUT1, 2, 3) must satisfy the following electrical rating.
• When connecting a conductive load (e.g. relay coil) to loads K1, K2 and K3, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
<Electrical Rating>
220-240 VAC, 10 mA or more, 1A or less
24 VAC, 10 mA or more, 1 A or less (non-conductive load)
C1
CN511
K1,K2
L1
L2
OUTPUT1
OUTPUT2
PJ20
TB1
The optional P.C. board should be connected to the header outdoor unit (U1).
Downloaded from
www.Manualslib.com
Header outdoor unit
Outdoor unit
interface PCB
SW16
CN511
ON
OFF
1 2 3 4
Connector cable 1
Connector on Interface side (green)
Relays
Error indication Lamp
Operation indication Lamp
Error output
Operation output
Connector on optional PCB side
Terminal block
manuals search engine
Locally procured
Optional PCB
TB1
C1
1
K1
OUTPUT1
2
3
PJ20
K2
OUTPUT2
4
5
OUTPUT3
Shield
6
wire