Toshiba MMY-MAP0804HT8-E Service Manual page 185

Multi type
Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

Outdoor 7-segment display
Main
remote
Check
controller
code
H07
H07
H08
H08
H15
H15
Downloaded from
www.Manualslib.com
Check code
Location
AI-NET central
of
control
detection
remote
Sub-code
controller
I/F
d7
01: TK1 sensor
I/F
error
02: TK2 sensor
error
03: TK3 sensor
error
04: TK4 sensor
error
05: TK5 sensor
error
d4
I/F
manuals search engine
Description
System status
Low oil level
All stop
Operating compressor
protection
detects continuous state of
low oil level for about 2 hours.
Error in
All stop
Sensor resistance is infinity
temperature
or zero (open/short circuit).
sensor for oil
level detection
All stop
Sensor resistance is infinity
or zero (open/short circuit).
All stop
Sensor resistance is infinity
or zero (open/short circuit).
All stop
Sensor resistance is infinity
or zero (open/short circuit).
All stop
Sensor resistance is infinity
or zero (open/short circuit).
TD2 sensor
All stop
Air discharge temperature of
miswiring
(TD2) does not increase
(incomplete
despite compressor 2 being
insertion)
in operation.
184
Error detection
Check items (locations)
condition(s)
<All outdoor units in
corresponding line to be
checked>
• Check balance pipe
service valve to confirm full
opening.
• Check connection and
installation of TK1, TK2,
TK3, TK4, and TK5
sensors.
• Check resistance
characteristics of TK1,
TK2, TK3, TK4, and TK5
sensors.
• Check for gas or oil leak in
same line.
• Check for refrigerant
entrapment inside
compressor casing.
• Check SV3A, SV3B,
SV3C, SV3D, SV3E, and
SV3F valves for defect.
• Check oil return circuit of
oil separator for clogging.
• Check oil equalizing circuit
for clogging.
• Check connection of TK1
sensor connector.
• Check resistance
characteristics of TK1
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TK2
sensor connector.
• Check resistance
characteristics of TK2
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TK3
sensor connector.
• Check resistance
characteristics of TK3
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TK4
sensor connector.
• Check resistance
characteristics of TK4
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TK5
sensor connector.
• Check resistance
characteristics of TK5
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check installation of TD2
sensor.
• Check connection of TD2
sensor connector and
wiring.
• Check resistance
characteristics of TD2
sensor.
• Check for defect in outdoor
P.C. board (I/F).

Hide quick links: