Outdoor 7-segment display
Main
remote
Check
controller
code
E31
E31
F01
F02
F03
F04
F04
F05
F05
F06
F06
F07
F07
Downloaded from
www.Manualslib.com
Check code
Location
AI-NET central
of
control
detection
remote
Sub-code
controller
I/F
A3-IPDU Fan
1
2 3
IPDU
01
O
02
O
O
O
03
O
04
05
O
O
06
O
O
07
O
O
O
O
08
CF
O
O
09
0A
O
O
O
O
O
0B
0C
O
O
O
O
O
0D
O
O
O
0E
0F
O
O
O
O
Symbol O
signifies site of
IPDU error.
Indoor
unit
0F
Indoor
unit
0d
Indoor
unit
93
I/F
19
I/F
A1
01:
I/F
TE1 sensor error
02:
TE2 sensor error
18
I/F
18
manuals search engine
Description
System status
IPDU
All stop
Communication is disrupted
communication
between IPDUs (P.C.
error
boards) in inverter box.
Indoor TCJ
Stop of
Sensor resistance is infinity
sensor error
corresponding
or zero (open/short circuit).
unit
Indoor TC2
Stop of
Sensor resistance is infinity
sensor error
corresponding
or zero (open/short circuit).
unit
Indoor TC1
Stop of
Sensor resistance is infinity
sensor error
corresponding
or zero (open/short circuit).
unit
TD1 sensor
All stop
Sensor resistance is infinity
error
or zero (open/short circuit).
TD2 sensor
All stop
Sensor resistance is infinity
error
or zero (open/short circuit).
TE1/TE2
All stop
Sensor resistance is infinity
sensor error
or zero (open/short circuit).
TL sensor error All stop
Sensor resistance is infinity
or zero (open/short circuit).
181
Error detection
Check items (locations)
condition(s)
• Check wiring and
connectors involved in
communication between
IPDU-I/F P.C. board for
bad contact or broken wire.
• Check for defect in outdoor
P.C. board (I/F, A3-IPDU
or Fan IPDU).
• Check for external noise.
• Check connection of TCJ
sensor connector and
wiring.
• Check resistance
characteristics of TCJ
sensor.
• Check for defect in indoor
P.C. board.
• Check connection of TC2
sensor connector and
wiring.
• Check resistance
characteristics of TC2
sensor.
• Check for defect in indoor
P.C. board.
• Check connection of TC1
sensor connector and
wiring.
• Check resistance
characteristics of TC1
sensor.
• Check for defect in indoor
P.C. board.
• Check connection of TD1
sensor connector.
• Check resistance
characteristics of TD1
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TD2
sensor connector.
• Check resistance
characteristics of TD2
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TE1/
TE2 sensor connectors.
• Check resistance
characteristics of TE1/TE2
sensors.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TL
sensor connector.
• Check resistance
characteristics of TL
sensor.
• Check for defect in outdoor
P.C. board (I/F).