Toshiba MMY-MAP0804HT8-E Service Manual page 187

Multi type
Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

Outdoor 7-segment display
Main
remote
Check
controller
code
L03
L04
L04
L05
L06
L06
L07
L08
L08
L09
L10
L10
L20
L28
L28
Downloaded from
www.Manualslib.com
Check code
Location
AI-NET central
of
control
detection
remote
Sub-code
controller
Indoor
unit
96
I/F
96
I/F
96
No. of priority
I/F
indoor units
96
Indoor
unit
99
Indoor
unit
99
Indoor
46
unit
I/F
88
AI-NET
Indoor
98
unit
I/F
46
manuals search engine
Description
System status
Duplicated
Stop of
There is more than one
indoor header
corresponding
header unit in group.
unit
unit
Duplicated
All stop
There is duplication in line
outdoor line
address setting for outdoor
address
units belonging to different
refrigerant piping systems.
Duplicated
All stop
More than one indoor unit
priority indoor
has been set up as priority
unit (as
indoor unit.
displayed on
priority indoor
unit)
Duplicated
All stop
More than one indoor unit
priority indoor
have been set up as priority
unit (as
indoor unit.
displayed on
indoor unit other
than priority
indoor unit)
Connection of
Stop of
There is at least one stand-
group control
corresponding
alone indoor unit to which
cable to stand-
unit
group control cable is
alone indoor
connected.
unit
Indoor group /
Stop of
Address setting has not been
addresses not
corresponding
performed for indoor units.
set
unit
Indoor capacity
Stop of
Capacity setting has not been
not set
corresponding
performed for indoor unit.
unit
Outdoor
All stop
Jumper wire provided on P.C.
capacity not set
board for servicing I/F P.C.
board has not been removed
as required for given model.
Duplicated
All stop
There is duplication in central
central control
control address setting.
address
Too many
All stop
There are more than four
outdoor units
outdoor units.
connected
186
Error detection
Check items (locations)
condition(s)
• Check indoor addresses.
• Check for any change
made to remote controller
connection (group/
individual) since indoor
address setting.
• Check line addresses.
• Check display on priority
indoor unit.
• Check displays on priority
indoor unit and outdoor
unit.
• Check indoor addresses.
• Check indoor addresses.
Note:
This code is displayed
when power is turned on
for the first time after
installation.
Set indoor capacity. (DN =
11)
Check model setting of P.C.
board for servicing outdoor
I/F P.C. board.
• Check central control
addresses.
• Check network adaptor
P.C. board (applicable to
AI-NET).
• Check No. of outdoor units
connected (Only up to 4
units per system allowed).
• Check communication
lines between outdoor
units.
• Check for defect in outdoor
P.C. board (I/F).