Toshiba MMY-MAP0804HT8-E Service Manual page 191

Multi type
Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

Outdoor 7-segment display
Main
remote
Check
controller
code
P19
P19
P20
P20
Downloaded from
www.Manualslib.com
Check code
Location
AI-NET central
of
control
detection
remote
Sub-code
controller
Detected
I/F
outdoor unit
No.
8
I/F
22
manuals search engine
Description
System status
4-way valve
All stop
Abnormal refrigerating cycle
reversing error
data is collected during
heating operation.
Activation of
All stop
Pd sensor detects pressure
high-pressure
equal to or greater than
protection
3.6MPa.
190
Error detection
Check items (locations)
condition(s)
• Check for defect in main
body of 4-way valve.
• Check for coil defect in 4-
way valve and loose
connection of its
connector.
• Check resistance
characteristics of TS1 and
TE1 sensors.
• Check output voltage
characteristics of Pd and
Ps pressure sensors.
• Check for wiring error
involving TE1 and TL
sensors.
• Check for defect in Pd
pressure sensor.
• Check service valves (gas
side, liquid side) to confirm
full opening.
• Check for defect in outdoor
fan.
• Check for defect in outdoor
fan motor.
• Check outdoor PMVs
(PMV1, 2, 4) for clogging.
• Check indoor/outdoor heat
exchangers for clogging.
• Check for short-circuiting
of outdoor suction/
discharge air flows.
• Check SV2 circuit for
clogging.
• Check for defect in outdoor
P.C. board (I/F).
• Check for defect in indoor
fan system (possible cause
of air flow reduction).
• Check opening status of
indoor PMV.
• Check indoor-outdoor
communication line for
wiring error.
• Check for faulty operation
of check valve in discharge
pipe convergent section.
• Check gas balancing SV4
valve circuit.
• Check SV5 valve circuit.
• Check for refrigerant
overcharging.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmy-map0804ht8zg-eMmy-map0804ht8z-eMmy-map1004ht8-eMmy-map1004ht8zg-eMmy-map1204ht8-eMmy-map1204ht8z-e ... Show all

Table of Contents