(Errors detected by IPDU featuring in SMMS-i standard outdoor unit - typical examples)
Outdoor 7-segment display
01: Compressor 1
F13
02: Compressor 2
03: Compressor 3
01: Compressor 1
H01
02: Compressor 2
03: Compressor 3
01: Compressor 1
H02
02: Compressor 2
03: Compressor 3
01: Compressor 1
H03
02: Compressor 2
03: Compressor 3
01: Compressor 1
P04
02: Compressor 2
03: Compressor 3
01: Compressor 1
P07
02: Compressor 2
03: Compressor 3
0 : IGBT circuit
1 : Position detection circuit error
3 : Motor lockup error
4 : Motor current detection
C : TH sensor error
P22
D : TH sensor error
E : Inverter DC voltage error
(outdoor fan)
Note: Although letters 0 to F appear
at locations indicated by " ",
please ignore them.
01: Compressor 1
P26
02: Compressor 2
03: Compressor 3
01: Compressor 1
P29
02: Compressor 2
03: Compressor 3
Note: The above check codes are examples only, and different check codes may be displayed depending on the outdoor unit configuration
(e.g. a Super heat recovery multi system). For details, see the service manual for the outdoor unit.
Downloaded from
www.Manualslib.com
Check code
Display of receiving unit
TCC-LINK
Indicator light block
central control
or main remote
Operation Timer Ready
Sub-code
controller
display
F13
H01
H02
H03
P04
P07
P22
P26
P29
manuals search engine
Typical fault site
Flash
Error in temperature
Temperature sensor built into indoor IGBT (TH)
ALT
sensor built into indoor
has been open/short-circuited.
IGBT (TH)
Inverter current (Idc) detection circuit detects
Compressor breakdown
overcurrent.
Compressor error (lockup) Compressor lockup is detected
Current detection circuit
Abnormal current is detected while inverter
error
compressor is turned off.
Activation of high-pressure
ALT
High-pressure SW is activated.
SW
Heat sink overheating
Temperature sensor built into IGBT (TH) detects
ALT
error
overheating.
ALT Outdoor fan IPDU error
Outdoor fan IPDU detects error.
Short-circuit protection for compressor motor
Activation of G-Tr (IGBT)
ALT
driver circuit components is activated (momentary
short-circuit protection
overcurrent).
Compressor position
Compressor motor position detection error is
ALT
detection circuit error
detected.