Display Of System Information - Toshiba MMY-MAP0804HT8-E Service Manual

Multi type
Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

(1)Display of System Information (Displayed on Header Outdoor Unit Only)
SW01 SW02 SW03
1
2
3
4
5
6
7
8
9
10
1
11
12
13
14
15
16
Downloaded from
www.Manualslib.com
Unused
System capacity
No. of outdoor units
No. of indoor units connected /
No. of units with cooling thermo ON
No. of indoor units connected /
No. of units with heating thermo ON
Amount of compressor command
correction
Release control
Oil equalization control
Oil equalization request
Refrigerant/oil recovery operation
3
Automatic addressing
Power pick-cut
Optional control (P.C. board input)
Optional control
(BUS line input)
Unused
manuals search engine
Display detail
A [...8]~[48]:8 to 48 HP
B [HP]
A [...1]~[...4]:1 to 4
B [...P]
A [...0.]~[48.]:0 to 48 (No. of units connected)
B [C...0]~[C48]:0 to 48 (No. of units with cooling thermo ON)
A [...0.]~[48.]:0 to 48 (No. of units connected)
B [H...0]~[H48]:0 to 48 (No. of units with heating thermo ON)
A Value displayed in hexadecimal format
B
A Normal: [r. ...], During release control: [r.1]
B –
Normal: [oiL-0]
During oil equalization control: [oiL-1]
A Displayed through LED segment lighting pattern
B
Display section A
Display section B
If element F shown on sketch at right turned on:
A
Header unit oil equalization request
F G
B
If element C shown on sketch at right turned on:
Follower unit oil equalization request
E
C
D
Dp
U1
U2
U3
U4
Outdoor unit No.
A Oil recovery in cooling: [C1], Normal: [C ...]
B Refrigerant recovery in heating: [H1], Normal: [H ...]
A [Ad]
B During automatic addressing: [... FF], Normal: [... ... ...]
A [dU]
B Normal: [... ... ...], During 50-90% capacity operation: [_50-_90]
While control is based on BUS line input: [E50-E90]
Displays optional control status
Operation mode selection: During priority heating (normal)
Priority cooling
Heating only
Cooling only
Priority given to No. of indoor units in operation
Priority given to specific indoor unit
External master ON/OFF: Normal
Start input
Stop input
Night operation: Normal
Start input
Snowfall operation: Normal
Start input
Same as above
A –
B –
226
A
B
A
B
. . .
h. .
. . .
c. .
. . .
H. .
. . .
C. .
. . .
n. .
. . .
U. .
.....
. . .
.1.
. . .
.0.
. . .
. .
.... . .
. .
1. . .
. .
..... .
. .
.1. .